Table 6-12

Speed Ramp Setup Menu (2260) Parameters

Parameter
ID
Accel time 1
2270
Decel time 1
2280
Accel time 2
2290
Decel time 2
2300
Accel time 3
2310
Decel time 3
2320
Jerk rate
2330
Table 6-13
Critical Frequency Menu (2340) Parameters
Parameter
ID
Skip center freq 1 2350
Skip center freq 2 2360
Skip center freq 3 2370
Skip bandwidth
2380
1
Skip bandwidth
2390
2
Skip bandwidth
2400
3
Table 6-14
Spinning Load Menu (2420) Parameters
Parameter
ID
Spinning load
2430
mode*
Scan end thresh‐
2440
old
NXGPro+ Control Manual
Operating Manual, A5E50491925A
Unit
Default
Min
sec
5.0
0.0
sec
5.0
0.0
sec
5.0
0.0
sec
5.0
0.0
sec
5.0
0.0
sec
5.0
0.0
0.1
0.0
Unit
Default
Min
Hz
15.0
0.0
Hz
30.0
0.0
Hz
45.0
0.0
Hz
0.0
0.0
Hz
0.0
0.0
Hz
0.0
0.0
Unit
Default
Min
Off
%
20.0
1.0
Parameter Assignment/Addressing
6.5 Options for Drive Menu (2) - first part
Max
Description
3200.0
Acceleration time 1 in seconds from zero to
rated speed.
3200.0
Deceleration time 1 in seconds from rated to
zero speed.
3200.0
Acceleration time 2 in seconds from zero to
rated speed.
3200.0
Deceleration time 2 in seconds from rated to
zero speed.
3200.0
Acceleration time 3 in seconds from zero to
rated speed.
3200.0
Deceleration time 3 in seconds from rated to
zero speed.
3200.0
Jerk rate in time to reach an acceleration rate
that will achieve rated velocity in 1 sec.
Max
Description
360.0
Enter the center of the first critical frequency
band to be avoided.
360.0
Enter the center of the second critical fre‐
quency band to be avoided.
360.0
Enter the center of the third critical frequen‐
cy band to be avoided.
6.0
Enter the bandwidth of the first critical fre‐
quency band to be avoided.
6.0
Enter the bandwidth of the second critical
frequency band to be avoided.
6.0
Enter the bandwidth of the third critical fre‐
quency band to be avoided.
Max
Description
Enable or disable spinning load and set the
direction of frequency scans:
Off
Forward
Reverse
Both; scans first in the forward direction,
then in the reverse direction.
50.0
The point where scan ends if motor flux is
above this level, as a percentage of motor
rated flux.
105