Selecting The Active Sop - Siemens SINAMICS PERFECT HARMONY GH180 Function Manual

Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Operating the Software

10.10 Selecting the active SOP

10.10
Selecting the active SOP
It is possible to store multiple system programs on the flash card. The purpose is for factory
testing or commissioning, as the SOP allows the drive to be run with minimal external
connections.
Note
Requirement when selecting the active SOP
To select a different active SOP, the drive must not be running.
This could cause drive instability and/or a trip.
Use the parameter Select system program (9146) to select from a pick list of all available SOPs.
To determine the SOP that is currently selected, use the Display sys prog name (9140) function.
Find both parameters under the SOP and Serial Functions Menu (9110).