Parameter Assignment/Addressing
6.5 Options for Drive Menu (2) - first part
Parameter
ID
Current Level
2450
Setpoint
Current ramp
2460
Max current
2470
Frequency scan
2480
rate
* If spinning load mode is disabled from this parameter, it will enable automatically on an as-
needed basis; this occurs only when fast bypass is enabled and only for the duration of the
bypass. This action is internal and does not require user intervention. This action does not
affect the spinning load mode paramete.
Table 6-15
Conditional Timer Setup Menu (2490) Parameters
Parameter
ID
Cond stop timer
2500
Cond run timer
2510
Table 6-16
Cell Menu (2520) Parameters
Parameter
ID
Installed cells/
2530
phase
Permitted min cell
2541
count
106
Unit
Default
%
15.0
sec
0.01
%
50.0
sec
3.00
Unit
Default
Min
sec
0.8
0.0
sec
0.8
0.0
Unit
De‐
Min
fault
4
1
12
3
Min
Max
1.0
50.0
0.00
5.00
1.0
50.0
0.00
5.00
Max
Description
999.9
Dwell time after stop is invoked. User function de‐
fined.
Not implemented
999.9
Dwell time after start is invoked. User function de‐
fined.
Not implemented
Max
Description
8
Number of installed cells per phase in the drive.
24
Set the permitted minimum cell count which establishes
the maximum number of cells that may be bypassed. At
least one cell must be operable in each phase.
A further restriction is enforced in the code to only allow
a maximum of nine cells in bypass. A bypass fault will
occur if the bypass operation attempts to exceed the
number.
Description
Set the drive current level (I
age of motor rated current, used during
scanning.
Time to ramp drive current (I
Level Setpoint.
Set the current trip level to abort spinning
load, as a percentage of motor rated current,
for scanning. Use the default value of 50 %.
Set the time taken to scan from rated speed
to zero. The default value of 3.00 sec is usu‐
ally satisfactory.