Comparator
Table 6-77
Comparator Setup Submenu
Submenu
Comparator n Setup
Note
Setting the SOP flag "DebounceComparators_O" adds a 100msec hysteresis to the setting and
clearing of all comparator flags. This should not be changed dynamically.
Table 6-78
Comparator Setup Menu Parameter Descriptions
Menu Item
Comp n A in variable select (list) (n=1-32) Manual value
Comp n B in variable select (list) (n=1-32) Manual value
Comp n manual value
Compare n type (list) (n=1-32)
Table 6-79
Variable Pick List for Comparator Setup Submenus
Manual Value
Analog Input 1
Analog Input 2
Analog Input 3
Analog Input 4
Analog Input 5
Analog Input 6
Analog Input 7
Analog Input 8
NXGPro+ Control Manual
Operating Manual, A5E50491925A
Description
Submenus that contain 32 sets of comparators for custom use
in the System Program. Each comparator set (Compare 1
through Compare 32) consists of three parameters that are
located in the comparator setup menus. Comparators are Sys‐
tem Program flags (Comparator1_I through Comparator32_I)
which can be used anywhere within the System Program en‐
vironment to control software switches.
Default Value
0.0%
'Mag' if n=1;'Off' if n>1
Analog Input 17
Analog Input 18
Analog Input 19
Analog Input 20
Analog Input 21
Analog Input 22
Analog Input 23
Analog Input 24
Motor Speed
Parameter Assignment/Addressing
6.11 Options for Auto Menu (4)
Description
"Comp n A" and "Comp n B" inputs can be
selected from the Table Variable Pick
List for Comparator Setup Submenus.
The comparator flag compar_n_f (where
n=1-16) in the System Program is set
true if "Comp n A in" > "Comp n B in var‐
iable select list.
Min: -1,000% Max: 1,000%
"Compare n" can be set to the following:
signed (e.g., 10 > -50)
magnitude (e.g., -50 > 10)
disabled (no compare is done)
Manual ID Number
Internal Analog Input 1
Internal Analog Input 2
Internal Analog Input 3
Internal Analog Input 4
Internal Analog Input 5
Internal Analog Input 6
Internal Analog Input 7
Internal Analog Input 8
147