Order
Code
Meaning
18
OVLT
Regen Limit for 6-step
19
BYPS
Cell bypassed
20
PRCH
Pre-charge
21
OLTM
Open loop test mode
22
MODE
Normal mode display
23
CURP
Current profile mode limit
24
OTRB
Over temperature rollback
25
TSRB
Transformer secondary
rollback
26
IPIT
Input interruption time test
failure
27
NT1R
Network1 regen limits
28
NT2R
Network2 regen limits
Table 9-5
Line 2 of mode field
Order
Code
Meaning
1
NOMV
No medium voltage
2
INH
CR3 inhibit
3
OFF
Idle state
4
MAGN
Magnetizing motor state
5
SPIN
Spinning load state
6
UXFR
Up transfer state
7
DXFR
Down transfer state
8
KYPD
Keypad speed demand
9
TEST
Speed/Torque test
10
LOS
Loss of Signal
11
NET1
Network 1
12
NET2
Network 2
13
AUTO
Automatic mode
14
HAND
Hand mode
15
BRAK
Dynamic Braking
16
DECL
Decelerating (no braking)
NXGPro+ Control Manual
Operating Manual, A5E50491925A
Description
Indicates that the six-step regeneration torque limit is in effect. It is set
when the cell voltage gets too high, and serves to reduce the regen torque
limit to limit the energy flow from the output (motor) to the cells to pre‐
vent cell overvoltage.
Indicates that one or more cells are in bypass.
One of the pre-charge modes is selected and the drive is pre-charging, or
ready to pre-charge.
Appears if drive control algorithm is set to open loop test mode.
This is the typical display message during normal operation.
Appears if the current limit is due to the current profile limit curve.
Occurs when cell OT and / or transformer OT switches are active.
Occurs when cell power is too high for secondary power ratings.
The input interruption time exceeded allowable limits or the function "Test
IP Interruption Time" (7126) has not been executed.
Regen limits commanded from Network 1.
Regen limits commanded from Network 2.
Description
No input line voltage detected.
The CR3 or "drive inhibit" input is asserted.
The drive is ready to run but is in an idle state.
The drive is magnetizing the motor or passing through the magnetizing
drive state.
The drive is trying to detect the speed of the motor in order to synchronize
the drive frequency.
The drive is in the "Up Transfer State" preparing to transfer the motor to the
input line.
The drive is in the "Down Transfer State" preparing to transfer the motor
from the input line to the drive.
The drive speed demand source is the keypad.
The drive is in a speed or torque test mode.
The drive 4 to 20 mA analog input signal has dropped below a predefined
setting.
Indicates drive is being controlled from Network 1.
Indicates drive is being controlled from Network 2.
The SOP flag AutoDisplayMode_O is set true usually to indicate drive is
receiving its speed demand from a source other than the keypad or net‐
work. Typically used with an analog input speed source. This mode is
entirely determined by setting the SOP flag. It does not affect NXG oper‐
ation.
Appears if the drive is running under normal conditions.
Indicates that dynamic braking is enabled.
The drive is decelerating normally.
Software user interface
9.1 SIMATIC Keypad