Hardware User Interface Description
5.3 User Accessible Interfaces
DO-xx*
Terminal
DO-13
J4-4, 5, 6
M1 DOUT
SIB 51, 53, 55 M1PermitClosed_I
* DO-xx: Refer to specific drive wiring diagram for DO-xx designations
5.3.12

Dedicated I/O for Input Protection (IP)

The following are dedicated I/O for input protection usage. Any cell type may use these
dedicated I/O if parameter Dedicated Input Protect (7108) is set "ON". If set to "OFF" this
dedicated I/O will not function unless air-cooled 6SR4_0 cells or water-cooled 6SR32x cells are
used. These cells must use dedicated inputs and outputs for IP faults, which are on by default.
Turning parameter Dedicated Input Protect (7108) off will be overridden by the software code
and still be active (on).
Table 5-7

Dedicated Inputs

DI-xx*
Terminal
DI-3E
J9-4
* DI-xx: Refer to specific drive wiring diagram for DI-xx designations
Table 5-8

Dedicated Outputs

DO-xx*
Terminal
DO-15
J4-10, 11, 12
M1 DOUT
SIB 51, 53, 55 M1PermitClosed_I
* DO-xx: Refer to specific drive wiring diagram for DO-xx designations
Cell Types when Dedicated I/O is not used
For all cell types that do not have dedicated I/O assignments or if the user I/O board is not used,
(i.e. when using WAGO I/O), internal digital I/O must be mapped to SOP flags associated with the
function. The flags are entirely controlled via the SOP.
80
SOP Feedback
InternalDigitalOutput13
SOP Feedback
InternalDigitalInput3e_I
SOP Feedback
InternalDigitalOutput3e_I
Function
BreakerTrip
M1Close Permissive
(TIMV)
Function
LFRInputProtectACK
Function
LFRInputProtect
M1Close Permissive
(TIMV)
Description
Command to open (trip) pre-
charge supply breaker
If this signal is de-energized, the
drive's medium voltage will trip
immediately.
If the signal is not energized, it
will be an inhibit.
Description
Latch Fault Relay (LFR) status
Description
Command to set LFR (1 sec
pulse)
If this signal is de-energized, the
drive's medium voltage will trip
immediately.
If the signal is not energized, it
will be an inhibit.