Troubleshooting Faults and Alarms
11.13 Dedicated I/O for Input Protection
Fault Display
Coolant Inlet Temp > 60°C
Coolant Inlet Temp < 22°C
Cell Water Temp High
Coolant Tank Level < 30 inches
490
Type
Enable
F/A
SOP
F/A
SOP
F/A
SOP
A
SOP
Potential Causes and Corrective Actions
Cause
Drive initiated alarm when the InletWaterTempHigh_O
SOP flag is set true and the InletWaterTempHighEn_O
flag is true to enable it. The default is an alarm but it can be
changed to a fault by setting
the InletWaterTempHighWn_O flag to False (true is an
alarm). This is used in the Standard SOP for water-cooled
drives as an alarm.
Action
1. Check physical input connected to SOP flag.
2. Check coolant temperature.
3. Check for flow.
Cause
Drive initiated alarm when the InletWaterTempLow_O
SOP flag is set true and the InletWaterTempLowEn_O flag
is true to enable it. The default is an alarm but it can be
changed to a fault by setting
the InletWaterTempLowWn_O flag to False (true is an
alarm). This is used in the Standard SOP for water-cooled
drives as an alarm.
Action
1. Check physical input connected to SOP flag.
2. Check coolant temperature.
3. Check for flow.
Cause
Drive initiated alarm when the CellWaterTempHigh_O
SOP flag is set true and the CellWaterTempHighEn_O flag
is true to enable it. The default is an alarm but it can be
changed to a fault by setting
the CellWaterTempHighWn_O flag to False (true is an
alarm). This is used in the Standard SOP for water-cooled
drives as an alarm.
Action
1. Check physical input connected to SOP flag.
2. Check coolant temperature.
3. Check for flow.
Cause
Drive initiated alarm when the LowWaterLevelAlarm_O
SOP flag is set true and the LowWaterLevelAlarmEn_O
flag is true to enable it. The default is an alarm and it cannot
be changed. This is used in the Standard SOP for water-
cooled drives as an alarm.
Action
1. Check physical input connected to SOP flag.
2. Check sensor.
3. Check and fill tank.
NXGPro+ Control Manual
Operating Manual, A5E50491925A