Setting Transmitter Alarm; Electrical Considerations - Emerson Rosemount 2051 Reference Manual

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Electrical Installation
September 2020
Configuring password with AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Within the LOI select the Configure Password button and follow the screen
Configuring LOI password using LOI
Figure 4-3: LOI Password
4.5

Setting transmitter alarm

On the electronics board is an alarm switch, reference
the steps below to change the alarm switch location:
Procedure
1. Set loop to manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide switch to desired position.
4. Replace transmitter cover; cover must be fully engaged to comply with explosion
4.6

Electrical considerations

Note
Make sure all electrical installation is in accordance with national and local code
requirements.
70
prompts.
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
proof requirements.
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN P
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
Figure 1
Rosemount 2051 Pressure Transmitter
Reference Manual
00809-0100-4107
PASSWORD
PASSWORD ENABLE
CHANGE PASSWORD
BACK TO MENU
EXIT MENU
for switch location. Follow