Troubleshooting
September 2020
Table 6-3: Status: Failed – Fix Now
Alert name
LCD display
screen
No Pressure
NO P
Updates
UPDATE
Electronics
FAIL
Board Failure
BOARD
Critical Sensor
MEMRY
Data Error
ERROR
Critical
Electronics
Data Error
Sensor Failure
FAIL SENSOR
Incompatible
XMTR
Electronics and
MSMTCH
Sensor
Table 6-4: Status: Maintenance – Fix Soon
Alert name
LCD display
screen
No
NO T
Temperature
UPDATE
Updates
Pressure Out of
PRES
Limits
LIMITS
Sensor
TEMP
Temperature
LIMITS
Beyond Limits
100
LOI screen Problem
NO PRESS
There are no pressure updates
from the sensor to the
UPDATE
electronics
FAIL
A failure has been detected in
the electronics circuit board
BOARD
MEMORY
A user written parameter does
ERROR
not match the expected value
A user written parameter does
not match the expected value
FAIL
A failure has been detected in
SENSOR
the pressure sensor
XMTR
The pressure sensor is
incompatible with the
MSMTCH
attached electronics
LOI screen
Problem
NO TEMP
There are no temperature
updates from the sensor to
UPDATE
the electronics
PRES OUT
The pressure is either above or
below the sensor limits
LIMITS
TEMP OUT
The sensor temperature has
exceeded its safe operating
LIMITS
range
Reference Manual
00809-0100-4107
Recommended action
Ensure the sensor cable connection
to the electronics is tight.
Replace the transmitter.
Replace the pressure transmitter.
Confirm and correct all parameters
listed in Device Information.
Perform a Device Reset.
Replace Pressure Transmitter.
Confirm and correct all parameters
listed in Device Information.
Perform a Device Reset.
Replace pressure transmitter.
Replace pressure transmitter.
Replace the pressure transmitter.
Recommended action
Ensure the sensor cable connection
to the electronics is tight.
Replace the pressure transmitter.
Check the transmitter pressure
connection to ensure it is not
plugged or the isolating diaphragms
are not damaged.
Replace the pressure transmitter.
Check the process and ambient
conditions are within –85 to 194 °F
(–65 to 90 °C).
Replace the pressure transmitter.
Rosemount 2051 Pressure Transmitter