Emerson Rosemount 2051 Reference Manual page 91

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Reference Manual
00809-0100-4107
Performing 4–20 mA/1–5 V output trim using LOI
Figure 5-6: 4–20 mA output trim using LOI
5.8.2
Performing digital-to-analog trim (4–20 mA/1–5 V
output trim) using other scale
The scaled 4–20 mA output Trim command matches the 4 and 20 mA points to a user
selectable reference scale other than 4 and 20 mA [for example, 2 to 10 volts if measuring
across a 500 Ω load, or 0 to 100 percent if measuring from a Distributed Control System
(DCS)]. To perform a scaled 4–20 mA output trim, connect an accurate reference meter to
the transmitter and trim the output signal to scale, as outlined in the output trim
procedure.
Performing a 4–20/1–5 V mA output trim using other scale
with a Field Communicator
From the HOME screen, enter the Fast Key sequence and follow the steps within the Field
Communicator to complete the 4–20 mA output trim using other scale.
Device Dashboard Fast Keys
Performing a 4–20 mA/ 1–5 V output trim using other scale
with AMS Device Manager
Procedure
1. Right select the device and under the Method drop down menu, move cursor over
2. Select Scaled Digital to Analog Trim.
3. Follow screen prompts to perform a 4–20 mA/ 1–5 V Output Trim.
Reference Manual
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Calibrate and select Analog Calibration.
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
3, 4, 2, 2
Operation and Maintenance
September 2020
CALIBRAT
ZERO TRIM
LOWER TRIM
UPPER TRIM
ANALOG TRIM
FACTORY RECALL
BACK TO MENU
EXIT MENU
91