Configuration
September 2020
Figure 2-6: Set Output with LOI
Figure 2-7: 4–20 mA HART Square Root Output Transition Point
A. Square root curve
B. Five percent transition point
C. Four percent transition point
2.6.3
Rerange the transmitter
The range values command sets each of the lower and upper range analog values (4 and
20 mA/1–5 Vdc points) to a pressure. The lower range point represents 0 percent of range
and the upper range point represents 100 percent of range. In practice, the transmitter
range values may be changed as often as necessary to reflect changing process
requirements.
Select from one of the methods below to rerange the transmitter. Each method is unique;
examine all options closely before deciding which method works best for your process.
Rerange by manually setting range points with a Field Communicator, AMS Device
Manager, or LOI.
20
EXTENDED MENU
VIEW CONFIG
CALIBRAT
ZERO TRIM
DAMPING
UNITS
TRANSFER FUNCT
RERANGE
SCALED VARIAB
LOOP TEST
ASSIGN PV
DISPLAY
TAG
EXTENDED MENU
ALARM SAT
EXIT MENU
VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
Reference Manual
00809-0100-4107
TRANSFER FUNCT
LINEAR TRANSFER
FUNCTION
SQR ROOT TRANSFER
FUNCTION
BACK TO MENU
EXIT MENU
Rosemount 2051 Pressure Transmitter