Basic Setup Of The Transmitter - Emerson Rosemount 2051 Reference Manual

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Configuration
September 2020
2.5.4
Verifying process variables configuration
This section describes how to verify that the correct process variables are selected.
Verifying process variables with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Verifying process variables with AMS Device Manager
Procedure
1. Right click the device and select Overview from the menu.
2. Select the All Variables button to display the primary, secondary, tertiary and
2.6

Basic setup of the transmitter

This section goes through the necessary steps for basic setup of a pressure transmitter.
When installing in DP level or DP flow applications, refer to
setup instructions.
2.6.1
Setting pressure units
The pressure unit command sets the unit of measure for the reported pressure.
Setting pressure units with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Setting pressure units with AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Select Manual Setup and select desired units from Pressure Units dropdown menu.
3. Select Send when complete.
Setting pressure units with a LOI
Follow
ENTER buttons to select desired unit. Save by selecting SAVE as indicated on the LCD
display screen.
18
quaternary variables.
Figure 2-5
to select desired pressure and temperature units. Use the SCROLL and
3, 2, 1
2, 2, 1, 1, 4
Rosemount 2051 Pressure Transmitter
Reference Manual
00809-0100-4107
Configuring scaled variable
for

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents