The LOI password can be configured and enabled/disabled by HART communication via a field
communicator, AMS Device Manager, or the LOI.
Configuring LOI password with field communicator
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
Configuring LOI password with AMS Device Manager
1.
2.
3.
Configuring LOI password using local operator interface
Figure 4-3. Local operator interface password
4.5

Setting transmitter alarm

On the electronics board is an alarm switch, reference Figure 4-2 on page 43 for switch location.
Follow the steps below to change the alarm switch location.
1.
2.
3.
4.
Electrical installation
Right click on the device and select Configure.
Under Manual Setup select the Security tab.
Within the Local Operator Interface click the Configure Password button and follow the
screen prompts.
EXTENDED MENU
VIEW CONFIG
CALIBRAT
ZERO TRIM
DAMPING
UNITS
TRANSFER FUNCT
RERANGE
SCALED VARIAB
LOOP TEST
ASSIGN P
DISPLAY
EXTENDED MENU
EXTENDED MENU
TAG
ALARM SAT VALUES
EXIT MENU
PASSWORD
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
Set loop to manual and remove power.
Remove transmitter housing cover.
Use a small screwdriver to slide switch to desired position.
Replace transmitter cover; cover must be fully engaged to comply with explosion proof
requirements.
Section 4: Electrical Installation
2, 2, 6, 5, 2
PASSWORD
PASSWORD ENABLE
CHANGE PASSWORD
BACK TO MENU
EXIT MENU
March 2014
43