Configuring password with AMS Device Manager
1. Right click the device and select Configure.
2. Under Manual Setup select the Security tab.
3. Within the LOI select the Configure Password button and follow the screen prompts.
Configuring LOI password using LOI
Figure 4-3. LOI Password
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
4.5

Setting transmitter alarm

On the electronics board is an alarm switch, reference
the steps below to change the alarm switch location.
1. Set loop to manual and remove power.
2. Remove transmitter housing cover.
3. Use a small screwdriver to slide switch to desired position.
4. Replace transmitter cover; cover must be fully engaged to comply with explosion proof requirements.
4.6

Electrical considerations

Note
Make sure all electrical installation is in accordance with national and local code requirements.
Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment.
Electrical Installations
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN P
TAG
ALARM SAT VALUES
PASSWORD
PASSWORD
PASSWORD
SIMULATE
PASSWORD ENABLE
HART REV
CHANGE PASSWORD
BACK TO MENU
BACK TO MENU
EXIT MENU
EXIT MENU
Electrical Installations
Figure 4-2 on page 37
for switch location. Follow
May 2017
39