Reference Manual
00809-0100-4107
Rerange with a pressure input source and a Field Communicator, AMS Device Manager,
LOI, or local zero and span buttons.
Manually rerange the transmitter by entering range points
Entering range points with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Entering range points with AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Select Manual Setup and select Analog Output.
3. Enter upper and lower range values in the Range Limits box and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Entering range points with a LOI
Reference
and ENTER buttons.
Figure 2-8: Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without
entering specific 4 and 20 mA (1–5 Vdc) points.
Rerange with an applied pressure source using a Field Communicator
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
Rerange with an applied pressure source using AMS Device Manager
Procedure
1. Right select the device, select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure button and follow the screen prompts range the
Reference Manual
Figure 2-8
to rerange the transmitter using the LOI. Enter values using SCROLL
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
transmitter.
2, 2, 2, 1
RERANGE
ENTER VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
2, 2, 2, 2
Configuration
September 2020
ENTER VALUES
LRV
URV
BACK TO MENU
EXIT MENU
21