Emerson Rosemount 2051 Reference Manual page 26

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents

Advertisement

Configuration
September 2020
Table 2-6: Custom Alarm and Saturation Values
Level
Low
High
Failure mode alarm and saturation levels can be configured using a Field Communicator,
AMS Device Manager, and the LOI. The following limitations exist for custom levels:
Low alarm level must be less than the low saturation level
High alarm level must be higher than the high saturation level
Alarm and saturation levels must be separated by at least 0.1 mA (0.025 Vdc)
The configuration tool will provide an error message if the configuration rule is violated.
Note
Transmitters set to HART
digitally; saturation and alarm conditions will not affect the analog output. See also
Establishing multidrop
Configuring alarm and saturation levels using a Field
Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Configuring alarm and saturation levels with AMS Device
Manager
Procedure
1. Right select on the device, and select Configure.
2. Select Configure Alarm and Saturation Levels button.
3. Follow screen prompts to configure Alarm and Saturation Levels.
Configuring alarm and saturation levels using LOI
Refer to
26
4–20 mA (1–5 Vdc) saturation
3.70 mA– 3.90 mA (.90 –.95 V)
20.10 mA –22.90 mA (5.025 –5.725 V)
®
multidrop mode send all saturation and alarm information
communication.
Figure 2-13
for instructions to configure alarm and saturation levels.
4–20 mA (1–5 Vdc) alarm
3.60–3.80 mA (.90 –.95 V)
20.20 mA – 23.00 mA (5.05 –5.75 V)
2, 2, 2, 5
Rosemount 2051 Pressure Transmitter
Reference Manual
00809-0100-4107

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents