Point Name/Description
System Occupancy – The status of the

Maintenance

Navigation:
i-Vu / Field Assistant:
BACview:
Point Name/Description
Unit
Occupancy Status – The controller's occupancy status as determined by a network
schedule, a local schedule, or a timed override.
Indicates the current status of the system:
Temp Compensated Start
Learning Adaptive Start
Space Temp Source – The source of the controlling space temperature value.
Options:
Sensor Failure – No valid space temperature or sensor status = failed.
SPT Sensor – An SPT sensor is connected to the controller's Rnet port.
T55/56 – A T55, T56, or T59 sensor is connected to the controller's J20 terminals.
Network – A network temperature sensor is bound to the controller's space
temperature AV.
Airside Linkage – The space temperature from a linked terminal.
Locked Value –The controller's space temperature input has been manually locked at
a value.
Setpoint Adjustment – The amount that a user has adjusted the setpoints at an SPT
space sensor.
Effective Heat Setpoint – The current heating setpoint.
Effective Cool Setpoint – The current cooling setpoint.
Relative Humidity Source – The source of the relative humidity.
IAQ Source – The source of the indoor air quality.
VVT Zone Controller
network point.
System Occupancy
Properties
Equipment
>
HOME
MAINT
>
Default/Range
D:
R:
Maintenance
>
Default/Range
R:
R:
R:
R:
R:
R:
R:
R:
Unoccupied
Unoccupied/Occupied
Unoccupied/Occupied
Inactive/Active
Sensor Failure
SPT Sensor
T55/T56
Network
Airside Linkage
Locked Value
-20 to 20°F
-56 to 245°F
-56 to 245°F
N/A
Local
Network
Linkage
Locked Value
N/A
Local
Network
Linkage
Locked Value
63