Parameter setting examples – ACS880
Speed control using the ABB Drives – Enhanced
communication profile
This example shows how to configure a speed control application
that uses the ABB Drives - Enhanced profile. In addition, some
application-specific data is added to the communication.
The start/stop commands and reference are according to the ABB
Drives profile. For more information, see section
communication profile
When Reference 1 (REF1) is used, a reference value of ±20000
(4E20h) corresponds to the reference set with parameter 46.01
Speed scaling in the forward and reverse directions.
The minimum and maximum 16-bit integer values that can be
given through the fieldbus are -32768 and 32767 respectively.
Output data
Control word
Speed reference
Reference 2 (Not used)
Constant speed 1 [32]
Constant speed 2 [32]
1)
Example
The table below gives the recommended drive parameter settings.
Drive parameter
50.01 FBA A enable
50.02 FBA A comm loss
func
50.03 FBA A comm loss t
out
on page 91.
Modbus
register
(4)00001
(4)00002
(4)00003
1)
(4)00004
(4)00005
1)
(4)00006
(4)00007
Setting for ACS880
drives
1 = Option slot 1
2)
1 = Fault
2)
3.0 s
Modbus/TCP – Start-up
ABB Drives
Input data
Status word
Speed actual value
Actual value 2 (Not used)
1)
Output power [32]
1)
DC voltage [32]
Description
2)
Enables communication between
the drive and the fieldbus adapter
module.
Enables fieldbus A
communication fault monitoring.
Defines the fieldbus A
communication break supervision
time.
85
Modbus
register
(4)00051
(4)00052
(4)00053
(4)00054
(4)00055
(4)00056
(4)00057