4.3.9.

Wireless zones configuration

4.3.9.1. Wireless sensors configuration
Wireless zones can be configured using complex service functions, after activation of which,
all the parameters related to the relevant zone can be given subsequently or in a form of
series of service functions that configure one zone-related parameter. Codes of zone
configuration functions are defined as per the following pattern:
Where:
XX –
determines the number of wireless zone from 01 to 16; entering number 00 will
change the parameters for all zones in the system,
Y – number of parameter related to a given zone:
 0 – complex function, the initiation of which configures the parameters listed below
as another set of parameters:
 1 – Delete a sensor. After selecting this option, you can confirm deleting by pressing
key, or you can cancel function by pressing
 2 – Add a sensor. After selecting this option, the sabotage button on the sensor has
to be pressed. Once the transmission with the sensor is established, its serial number
will be displayed on the keypad (hexadecimal value). If accepted, the sensor will be
saved.
3 – Type of a wireless sensor (read only):
o 0 – no sensor
o 1 – PIR-10 sensor
o 2 – MC-10 sensor
o 3 – GS-10 sensor
o 4 – SD-10 sensor
o 5 – PIR-11 sensor
o 6 – SD-20 sensor
o 7 – KP1W keypad
o 8 – MC-11 sensor
o 9 – FL-10 sensor
Note: During the adding a new wireless detector (function 2), the front cover of the detector
should be removed. It is recommended to add wireless sensors individually. To prevent the
accidental transmissions from other detectors, only one detector cover should be removed
during the procedure of adding a new detector.
Example:
a) delete a wireless sensor no. 10:
b) add a wireless sensor no. 11:
CPX220NWB ALARM CONTROL UNIT – INSTALLER MANUAL
<XX> <Y>
key.