EBS CPX200NWB Installation And Programming Manual

EBS CPX200NWB Installation And Programming Manual

Alarm control unit
Table of Contents

Advertisement

Quick Links

ALARM CONTROL UNIT
CPX200NWB
Installation and
programming manual
Version of the manual:
Date of issue:
Firmware version:
GPRS transmitter configurator version:
OSM server version:
v1.17
2016.06.24
2.4.13
1.3.60.3
1.3.59.1

Advertisement

Table of Contents
loading

Summary of Contents for EBS CPX200NWB

  • Page 1 ALARM CONTROL UNIT CPX200NWB Installation and programming manual Version of the manual: v1.17 Date of issue: 2016.06.24 Firmware version: 2.4.13 GPRS transmitter configurator version: 1.3.60.3 OSM server version: 1.3.59.1...
  • Page 2 DECLARATION OF COMPLIANCE We, EBS Sp. z o.o., declare with full responsibility that the present product meets all requirements provided for in the Directive 1999/5/EC of European Parliament and Council dated 9 March 1999. The copy of the “Declaration of Compliance”...
  • Page 3: Table Of Contents

    5.3.2. MENU -> OPERATIONS ......................49 5.3.3. MENU -> HELP ........................51 5.4. DEVICE PROGRAMMING ........................51 5.4.1. LOCAL PROGRAMMING ......................51 5.4.2. REMOTE PROGRAMMING ......................51 PROGRAMMABLE PARAMETERS....................53 CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 3 / 118...
  • Page 4 NETWORK LOG-IN .......................... 92 7.2. GSM RANGE ........................... 92 7.3. TRANSMISSION ..........................92 7.4. PROGRAMMING ..........................93 7.5. FIRMWARE UPDATE ........................93 7.6. NO SIM CARD OR SIM CARD DAMAGED ................... 93 CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 4 / 118...
  • Page 5 DRAWING 7. CONTROL PANEL HORIZONTAL LOCATION .................. 21 DRAWING 8. CONTROL PANEL VERTICAL LOCATION ..................21 DRAWING 9. SIGNAL LOSS THROUGH CONSTRUCTION MATERIALS ..............22 DRAWING 10. SENSOR PLACEMENT ........................ 22 CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 5 / 118...
  • Page 6: Introduction

    1. INTRODUCTION Thank you for choosing EBS alarm control unit. CPX200NWB is a simple, functional alarm control unit integrated with GSM/GPRS/SMS transmitter, intended for small- and medium- sized facilities. The central unit is equipped with 3 outputs and 16 zones with the possibility to be divided into 2 partitions. Dedicated KP16 LED keypad was designed in a modern, discreet style.
  • Page 7: Control Unit Functions

     Possibility to restrict the scope of authorization to a few codes only SYSTEM OPTIONS  Automatic diagnosis of basic system components  Possibility to review faults, alarm memories, event log  System/technical event history – min. 5000 events CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 7 / 118...
  • Page 8: Specifications

    Lead-acid 12V Low voltage – event treshold: Voltage battery cut off level: below 9V Working temperature: -10ºC to +55ºC Working humidity: 5% to 93% PCB dimensions: 152mm x 78mm x 30mm CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 8 / 118...
  • Page 9: Installation And Wiring

    NOTE: If you use more than one keyboard in the system, be sure to address each assignment of the keyboard (see chapter 3.6.4.). 9. Verify the operation of the system and all its components. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 9 / 118...
  • Page 10: Description Of Pcb Elements

    (especcialy wires). Don’t put antennas into cases (above all in metal cases). Antenna wire shouldn’t be flexed or rucked. There is not recommend to extend antenna wire. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 10 / 118...
  • Page 11 9. Screw terminals of the control unit For detailed information on feeding, input and output connectors, please refer to chapter 3.3. Assembly holes of the control unit (132x61mm hole span) CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 11 / 118...
  • Page 12 OBDNA casing can be ordered (the casing includes appropriate 230VAC/18VAC transformer). Wireless module antenna connector CPX200NWB included two types of antennas: internal and external dipole type. 433MHz internal antenna Internal antenna can be used wherever required compact size and antenna provides appropriate coverage level detectors.
  • Page 13 GND socket. Correct install position for dipol antenna in the attached photo below. Wireless module The wireless module is used to receive signals from remote controls and wireless detectors. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 13 / 118...
  • Page 14: Description Of Screw Terminals Of The Control Unit

    3.3. DESCRIPTION OF SCREW TERMINALS OF THE CONTROL UNIT NOTE: Any assembly and installation works shall be carried out with power supply off and battery disconnected. Drawing 2. Description of screw terminals of the control unit CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 14 / 118...
  • Page 15: Configuration Of Wired Input Lines

    (DEOL-NO or DEOL-NC) using 1.1kΩ resistors. Both resistor types are included in the delivery of the control unit. Various configurations of input lines are presented in the drawing 3. Drawing 3. Configuration of input lines CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 15 / 118...
  • Page 16: Sample Connection Of Signalling Device

    3.5. SAMPLE CONNECTION OF SIGNALLING DEVICE 3.5.1. Internal signalling device without independent source of power supply Drawing 4. Sample connection of internal signalling device without independent source of power supply CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 16 / 118...
  • Page 17: External Signalling Device With Independent Source Of Power Supply

    3.5.2. External signalling device with independent source of power supply Drawing 5. Sample connection of external signalling device with independent source of power supply CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 17 / 118...
  • Page 18: Kp16 Keypad

    2. ALARM LED (red): Flashing light – means that alarms were present in the system (alarm memory). Constant light – means that system is in alarm state. Off – system is operating correctly. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 18 / 118...
  • Page 19 After the keypad is assembled the switch contact is closed. Unauthorized disassembly of the keypad will send the message to the alarm control unit. In order to eliminate surface unevenness, a spring is located on the switch lever. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 19 / 118...
  • Page 20: Keypad Specification

    , which means a new keypad address. 3. After about 5 seconds the keypad will display the programmed keypad address. 4. After programming the keypad address, reset the control panel CPX200NWB. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 20 / 118...
  • Page 21: Control Panel Location

    Medium attenuation have light concrete and brick walls. Reinforced concrete and metal latticed plaster have the greatest attenuation. The drawing 9 shows the signal loss through various different types of materials. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 21 / 118...
  • Page 22: Wireless Detectors Installation Recommendations

    In this way you get the best radio coverage. Additional installation tips describes the drawing 10. Drawing 10. Sensor placement CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 22 / 118...
  • Page 23: Service Mode

    1 2 3 4 6 7 8 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 6 7 2 3 4 5 6 7 CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 23 / 118...
  • Page 24: Activation Of Service Mode

    Remote controllers configuration <XX> <Y> Emergency buttons <XX> <Y> 4.3.1. Installer code The installer code can be changed here. 3 beeps will confirm the successfully entered function. <Installer code> <Installer code> where: CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 24 / 118...
  • Page 25: Power Loss

     4 – Access to alarm and fault memory requires authorization. If this option is enabled, checking alarm memory and fault memory is available only after a user code CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 25 / 118...
  • Page 26: Users Remote Management

    Wired and wireless zones can be configured using complex service functions, after activation of which, all the parameters related to the relevant zone can be given subsequently or in a CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 26 / 118...
  • Page 27 3 – interlocking the zone (bypassing zone) if the zone violated when arming (parameter “After time for exit”)  6 – sensitivity in milliseconds, i.e. after what time the input is considered to change its status – default value; 400ms CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 27 / 118...
  • Page 28: Outputs Configuration

     0 – complex function, the initiation of which configures the parameters listed below as another set of parameters;  1 – type of output (DEC type parameter): o 0 – not used, CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 28 / 118...
  • Page 29: Partitions Configuration

    , will not be cancelled. 4.3.8. Partitions configuration Partition configuration can be configured similarly as zones and outputs, using complex service functions after activation of which, all the parameters related to the relevant CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 29 / 118...
  • Page 30 Eg. If the auto-arming time is set to 2:30, and time was changed forward from 2:00 to 3:00, the control panel will not arm. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 30 / 118...
  • Page 31: Wireless Zones Configuration

    01 to 16; entering number 00 will change the parameters for all zones in the system, Y – number of parameter related to a given zone: CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 31 / 118...
  • Page 32 3 LEDs – 37% signal strength 4 LEDs – 50% signal strength 5 LEDs – 62% signal strength 6 LEDs – 75% signal strength 7 LEDs – 88% signal strength CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 32 / 118...
  • Page 33: Remote Controllers Configuration

    1 – P300 remote control o 2 – RC-10 remote control  4 – The use to which the remote control is assigned  5, 6, 7, 8 – buttons functions: CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 33 / 118...
  • Page 34: Emergency Buttons

    3 beeps and exit the function. If you press key will exit the function and remote controllers will not be erased. 4.3.11. Emergency buttons To configure emergency buttons, use the following pattern: <XX> <Y> where: – emergency button: CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 34 / 118...
  • Page 35: Text Messages Configuration

    CPX200NWB can store up to 10 phone numbers and up to 32 text messages. If, for any reason, the SMS can not be send at the moment, it will be send as soon as the connection with the GSM network is re-established but not later than 1 day after the occurrence of the event triggering SMS send request (text messages get expired and are deleted).
  • Page 36 VALUE – new name of the partition Example 1: 1234 SETNAME=PARTITION,1,Cellar Example 2: 1234 SETNAME="PARTITION,2,Kids Room" Feedback message SETNAME::OK or SETNAME:ERROR Feedback message SETNAME::OK – command accepted description SETNAME:ERROR – command rejected by the system CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 36 / 118...
  • Page 37 NUMBER – phone number, on which the texts will be send Example: 1234 SETTELNUM=3,800123456 Feedback message SETTELNUM:OK SETTELNUM:ERROR Feedback message SETTELNUM:OK – command accepted description SETTELNUM:ERROR – command rejected by the system CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 37 / 118...
  • Page 38 ID – index of text, possible values: 1 to 32 MESSAGE – content of the text message Example: 1234 SETMESSAGE=4,Robbery Feedback message SETMESSAGE:OK or SETMESSAGE:ERROR Feedback message SETMESSAGE:OK – command accepted description SETMESSAGE:ERROR – command rejected by the system CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 38 / 118...
  • Page 39 ID – index of text, possible values: 1 to 32 Example: 1234 GETMESSAGE=30 Feedback message GETMESSAGE=ID,MESSAGE GETMESSAGE:ERROR Feedback message GETMESSAGE=ID,MESSAGE – information about the description contents of text message GETMESSAGE:ERROR – command rejected by the system CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 39 / 118...
  • Page 40 6 will be sent to phone numbers with indexes 1,8 and 9. Feedback message SETUSERSMS=EVENT,TELNUM,MSG_ID:OK SETUSERSMS=EVENT,TELNUM,MSG_ID:ERROR Feedback message SETUSERSMS=EVENT,TELNUM,MSG_ID:OK – description command accepted SETUSERSMS=EVENT,TELNUM,MSG_ID:ERROR – command rejected by the system CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 40 / 118...
  • Page 41 Example: 1234 GETUSERSMS=ARM1 Feedback message GETUSERSMS=EVENT:TELNUM,MSG_ID GETUSERSMS=EVENT:ERROR Feedback message GETUSERSMS=EVENT:TELNUM,MSG_ID – description information about text message and phone number assinged to the event GETUSERSMS=EVENT:ERROR – command rejected by the system CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 41 / 118...
  • Page 42 (to OUTPUT3-TAMPER) OUTPUT1-TAMPEREND Fault of zones 1…3 ended (to OUTPUT3-TAMPEREND) POWER-FAIL Power failure POWER-OK Power failure ended BATTERY-FAIL Battery failure BATTERY-OK Battery failure ended AUX1-FAIL Failure of auxiliary output 1 CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 42 / 118...
  • Page 43 List of errors sent as feedback messages Alias name Description ERROR-PERMISSION Permission to issue this command was not granted ERROR-FORMAT Wrong command syntax ERROR-VALUE Wrong parameter value ERROR-EMPTY Parameter value missing ERROR Other error CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 43 / 118...
  • Page 44: Configuration Wizard

    5.1. PRELIMINARY NOTES The configuration wizard of GPRS transmitters can be downloaded from www.ebs.pl (login: ebs, password: ebs). Activate the option of installation wizard which leads through the program installation process. By default it will be installed in C:\Program Files\EBS\ directory.
  • Page 45: Menu -> File

    Opens a new set of parameters. In this option configuration parameters of the equipment can be edited. Select a relevant type of the equipment: CPX200NWB 5.3.1.2. File -> Open If you have a file with recorded settings you can use it for programming another equipment.
  • Page 46 Click [Add] button to confirm the setting. The connection is saved (and moved to the table). From that moment the program will enable a wire connection with the equipment and allows reading and recording the parameters in the equipment’s memory. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 46 / 118...
  • Page 47 Connection function (or clicking icon on a taskbar) and opening GSM Modem tab.  The window will be displayed on the screen where you define:  Connection name, e.g. RemoteCSD CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 47 / 118...
  • Page 48 C:\Program Files\EBS\KonfiguratorLX\configs\CPX200NWB_20000\ CPX200NWB_20000 directory contains all files related to programming the CPX200NWB type device of the serial number 20000. Files names contain date and time of the operation and its type (recording/reading). The files are recorded with .cmi extension.
  • Page 49: Menu -> Operations

    It is also possible to set internal timer of the device. For the above you have to check the box “Set the time” and enter a respective date and time. A correct entry is confirmed with a relevant message. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 49 / 118...
  • Page 50 The function enables to read out the events lately recorded in the memory of the equipment. Please refer to chapter 6.12. 5.3.2.5. Operations -> Equipment monitoring The function allows the on-going monitoring of the equipment condition. Please refer to chapter 6.11. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 50 / 118...
  • Page 51: Menu -> Help

    (and sends) information only from equipment that is registered in its database, the first operation you have to do for remote programming it to properly register the equipment. The procedure is described in OSM.2007 user manual. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 51 / 118...
  • Page 52  Close the configuration wizard’s window after you finish the data input.  The equipment is ready for data transmission in accordance with new settings. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 52 / 118...
  • Page 53: Programmable Parameters

     GPRS: GPRS transmission (TCP/IP protocol) in standard. In case of any problems with that connection, no remote connection is possible  No server connection: no transmission with server, remote communication with a user is possible only via SMS messages CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 53 / 118...
  • Page 54: Access Point Name

    It defines the name of access point to GPRS network. There is a possibility to obtain a private access point. In this case its name will be given by a particular GSM network operator. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 54 / 118...
  • Page 55: Primary Server Parameters

    After a defined number of attempts, the equipment will initiate the procedure of connecting with secondary server. The option is active only in case the secondary server parameters were defined. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 55 / 118...
  • Page 56: Secondary Server Parameters

    (in TCP/IP or SMS mode). Default factory setting is 0000. It should be changed at first equipment start-up (programming). The code can be composed of from four to seven digits. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 56 / 118...
  • Page 57 PUK code (using any GSM phone). Default factory PIN code entered in the equipment is: 1111. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 57 / 118...
  • Page 58: Transmission

    GPRS and SMS transmissions. In case encrypted transmission was selected, you can enter own data encryption key (DEK) (256 bits - 0-9 and A-F characters) or use default setting. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 58 / 118...
  • Page 59: Inputs / Outputs

     Instant – disruption of the line causes immediate alarm, if the system is armed.  Delay – that type of line is usually used for detectors operation at the facility entries. The line switches into alarm state after the expiration of programmed CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 59 / 118...
  • Page 60 If this is not violated during exit time countdown, partition will be armed in the stay mode. If the system is armed, this zone behaves like the delayed zone. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 60 / 118...
  • Page 61 6.3.1.4. Sensitivity That parameter defines a minimum time the change must maintain at the particular zone, to be detected by a transmitter. Default factory setting of the parameter is 400 ms. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 61 / 118...
  • Page 62 Enabling this option causes the panel immediately generates an alarm when the zone was violated when the system is armed. 6.3.1.7. Ignore during arming Zone can be violated during partition arming (e.g. delay circuits shall be set to that option). CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 62 / 118...
  • Page 63: Wireless Zones

    6.3.2. Wireless zones CPX200NWB is capable of storing information about up to 16 wirelles inputs number from 1 to 16. Remove the front cover of the detector that you want to enroll to the control panel. It is recommended to add wireless sensors individually. To prevent the accidental transmissions from other detectors, only one detector cover should be removed during the procedure of adding a new detector.
  • Page 64 A new window appears. Configurator will be waiting for a wirells signal to come. User has to press for a while the tamper switch on the sensor. CPX200NWB will detect the transmission and print sensor’s type and ID. Add Device To bind this sensor with the Alarm Control Unit, press .
  • Page 65 Sensor preferences can be set now in the Inputs tab. You can choose the same options as for wired zones excluding sensitivity. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 65 / 118...
  • Page 66: Partitions

    6.3.3.4. Alarm time The parameter defines the time the alarm will be indicated by KP16 keypad. 6.3.3.5. Partition name The parameter allows you to give any name for the partition. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 66 / 118...
  • Page 67 NOTE: To use the auto-arming/disarming function, you should do a firmware upgrade to version 2.4.7 or higher, then read and write the configuration of the device using “GPRS transmitters configurator” program in version 1.3.57.3 or higher. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 67 / 118...
  • Page 68: Outputs

    40ms. In the case of set time for exit chirp is generated after arming, similarly in the case of the time for entry chirp is generated after disarming.  Alarm & chirp – The output is activated when alarm is detected or when arming/disarming. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 68 / 118...
  • Page 69: Remote Controllers

    Pressing OK will invoke new window indicating, that CPX200NWB is waiting for incoming tranmisson from the remote controller. User has to press one of the controller button, in order to bind it with the Alarm Control Unit. Device’s CPX200NWB ALARM CONTROL UNIT –...
  • Page 70 For normal and silent alarm can be sent a message to the monitoring station, depending on the configuration of the control panel. The control panel allows you to assign remote control buttons to various functions. It is possibile to configure different alarm button. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 70 / 118...
  • Page 71: Emergency Buttons

    User can choose which outputs should be turned on in case of the emergency button activation (pressing and holding a button for 3 seconds). Each of the outpus has the reminder of it’s function chosen in the “Outputs” tab. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 71 / 118...
  • Page 72: System Options

    Checking alarm memory and fault memory will be available only after entering user code. This option must be enabled in order to comply with EN 50131 standard requirements for Grade 2. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 72 / 118...
  • Page 73: Alarms And Inputs Interlocking States Are Not Displayed

    This option allows user managing. To be able to manager the users one has to press the ‘Edit’ button first and the input the correct administrator code. Granted the authorization, it will be possible to edit the users’ passwords and partition priviliages. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 73 / 118...
  • Page 74: Monitoring

    That option allows determining which of available signals generated by the equipment will be transmitted to the monitoring station. NOTE: The “Configuration change” event refers to configuration change via SMS or via GPRS instructions only. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 74 / 118...
  • Page 75: Events

    (normalisation). In order to transmit a particular signal you have to check it (by clicking a relevant check box on the right hand side). Press [Clear] button to remove all checked signals. Press [Reverse] to reverse the check into the opposite ones. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 75 / 118...
  • Page 76: Additional Data

     GSM status – status about connection to GSM network, type of connection to server (GPRS/SMS), information about ongoing phone calls  GSM signal level quality – quality of connection to GSM network (CSQ and BER parameters) CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 76 / 118...
  • Page 77: Restrictions

    To remove the number from the table, place the cursor in a particular number line and click [Remove]. “Remove all” option will clear all the numbers from the table. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 77 / 118...
  • Page 78  SMS tests to server  SMS events sent to server  SMS events sent to the user  Replies to commands CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 78 / 118...
  • Page 79 SMS, e.g. in case of a fault.  Counter reset: That parameter defines time (in minutes) after which the counter of SMS sent is to be reset. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 79 / 118...
  • Page 80: Remote Commands

    6.7.2. Remote commands 6.7.2.1. Users remote management enable Selecting this option allows you to remotely configure user accounts.
  • Page 81: Sms Notifications

    6.8. SMS NOTIFICATIONS 6.8.1. Phones CPX200NWB can notify users about occurrence of certain events by text message. Before sending the message, may occur an additional attempt a voice call (see item 6.8.4. Options). In order to add user’s number to the notification list, one has to type in the number next to the number index.
  • Page 82: Messages

    In text messages can be used only alphanumeric characters, as well as: ! @ # $ % " < > & * ( ) + : ? ` ; ' = , . / and space. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 82 / 118...
  • Page 83: Events

    From now on, whenever this event occurs, a text containing selected message will be send to the selected phone numbers. Before sending the message, may occur an additional attempt a voice call (see item 6.8.4. Options). CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 83 / 118...
  • Page 84: Options

    Note: The producer does not recommend using this option because it reduces security of the system. The option for use only by advanced users. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 84 / 118...
  • Page 85 CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 85 / 118...
  • Page 86: Sms Forward

    NOTE: The user is responsible for correct entering the telephone numbers that prevents any turmoil in sending SMS messages. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 86 / 118...
  • Page 87: Link Control

     Device reset In case the equipment lost the GSM connection, it shall wait for a defined period of time after the fact was ascertained and then it shall perform stipulated tasks. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 87 / 118...
  • Page 88: Gprs

    The equipment has integrated bootloader that enables module software update. During the programming all that process information is displayed. The following activities shall be performed:  Start configuration wizard,  Go to wizard’s “Firmware” option, CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 88 / 118...
  • Page 89: Device Monitoring

    GD-PROG cable in DEBUG mode and then, in “Port” box select an appropriate RS232 port. Monitor allows the control of the following parameters:  Condition of mains power supply  GSM network signal strength and bit error ratio (BER) CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 89 / 118...
  • Page 90: Events History

    “Read” button. After correct reading you will get the access to “Filtering” and “Graphs” functions which allow you a quick diagnosis of the equipment. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 90 / 118...
  • Page 91 CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 91 / 118...
  • Page 92: Led Indication

    GSM range = 8 GPRS mode GSM range = 6 SMS mode 7.3. TRANSMISSION During data transmission green LED indicates the data sending. LEDs Description ERROR STATUS (green) (red) (yellow) GPRS transmission transmission CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 92 / 118...
  • Page 93: Programming

    During the equipment’s operation errors can occur. Error is indicated by constant light of red LED and most often it means a communication problem with a modem or SIM card. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 93 / 118...
  • Page 94: Grade 2 Settings

    - Input 1 – 16 tamper - Output 1 – 3 tamper - Power - Battery - Jamming - Keypad output failure - Output AUX1 failure - Output AUX2 failure CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 94 / 118...
  • Page 95: The Behavior Of The System In Compatibility Mode For Grade 2

     the codes in the system must be at least 5 characters  after entering an invalid code three times, all keypads in the system will be blocked for 90 seconds. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 95 / 118...
  • Page 96: Extras

    However, there are parameters, changes to which will be detected only in special circumstances, for example – the server address. If it is changed when the device is online, a restart is needed. When CPX200NWB boots up, it will connect to the newly configured address.
  • Page 97 Sets the phone number for sending SMS with the events in the absence of GPRS communication. If the number is not configured sending SMS messages will not be available. Phone_number may contain a prefix of the country. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 97 / 118...
  • Page 98: General Commands

    Restarts the whole device. This results in breaking a GPRS session and deregistration from the GSM network and re-registering to GSM and GPRS network when you restart the device and modem. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 98 / 118...
  • Page 99 PORT – OSM server port APN – APN name by means of which the GPRS session is compiled UN – APN user name PW –APN password DNS0 –DNS server address CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 99 / 118...
  • Page 100 This command is a tool with which you can get information about the phone number of the SIM card installed in the device when connected to the OSM server using GPRS. 9.1.2.9. GETSTATUS Format: GETSTATUS CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 100 / 118...
  • Page 101: Commands For Managing The Users In Cp

    Battery_voltage – battery voltage in mV (12000 = 12V). If the battery is not connected, the readings may be incorrect, and be around 9V (9000) voltage_AC – AC voltage at the AC terminals of CPX200NWB (downstream the transformer) in mV (18000 = 18V) blocked_zones –...
  • Page 102 This command only works when sent through an encrypted way and the option “Allow remote user management” is set to active in the Configurator. Possible to execution only by ATS. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 102 / 118...
  • Page 103 If the specified password is incorrect CPGETUSERID:ENOT_ALLOWED If the command is sent via open SMS or the configuration does not allow remote management of users CPGETUSERID:EFORMAT If the format of the sent command is incorrect CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 103 / 118...
  • Page 104 If the administrator password specified is incorrect CPSETUSERPARTITIONS:ENOT_ALLOWED If the command is sent via open SMS or the configuration does not allow remote management of users CPSETUSERPARTITIONS:EFORMAT If the format of the sent command is incorrect CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 104 / 118...
  • Page 105 If the new password is too short or too long or does not consist of digits CPSETUSERPASSWORD:ENOT_ALLOWED If the command is sent via open SMS or the configuration does not allow remote management of users CPSETUSERPASSWORD:EFORMAT If the format of the sent command is incorrect CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 105 / 118...
  • Page 106 If the new password is too short or too long or does not consist of digits CPADDUSER:ENOT_ALLOWED If the command is sent via open SMS or the configuration does not allow remote management of users CPADDUSER:EFORMAT If the format of the sent command is incorrect CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 106 / 118...
  • Page 107 CPDELUSER:ENOT_ALLOWED If the command is sent via open SMS or the configuration does not allow remote management of users CPDELUSER:EFORMAT If the format of the sent command is incorrect CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 107 / 118...
  • Page 108 If the new password is too short or too long or does not consist of digits CPSETADMINPASSWORD: EPERMISIONS If the password can not be changed because it is already used by another user. If you type the current administrator password, the command returns EOK. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 108 / 118...
  • Page 109: Commands For Managing The Partitions, Zones And Outputs

    1 means the zone/output 1). If the partition is armed or counts down, the time to output the corresponding bit is set. Outputs – means the current status of outputs. It is a bit-vector, where bit CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 109 / 118...
  • Page 110 – battery voltage in mV (12000 = 12V). If the battery is not connected, the readings may be incorrect, and be around 9V (9000) powerSupplyVoltage – AC voltage at AC terminals of CPX200NWB (downstream the transformer) in mV (18000 = 18V).
  • Page 111 1 – configuration memory failure CPGETFAILURES:EPERMISIONS If the specified password is incorrect CPGETFAILURES:ENOT_ALLOWED If the command was sent via open SMS CPDELUSER:EFORMAT If the format of the sent command is incorrect CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 111 / 118...
  • Page 112 CPSETPARTITIONS=[STAY,]partitions,password:EFORMAT If the data format is incorrect (partitions,password are the command arguments) CPSETPARTITIONS=[STAY,]partitions:EPERMISIONS If the user with the specified password does not exist CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 112 / 118...
  • Page 113 , if the user does not have permissions to desired partitions). CPUNSETPARTITIONS=partitions,password:EFORMAT If the data format is incorrect (partitions,password are the command arguments) CPUNSETPARTITIONS=partitions:EPERMISIONS If the user with the specified password does not exist CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 113 / 118...
  • Page 114 If the format of the sent command is incorrect CPZONESLOCK:EPERMISIONS If the user has not authorization to the proper partition CPZONESLOCK:ENOT_EXISTS If the user with the specified password does not exist CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 114 / 118...
  • Page 115 If the format of the sent command is incorrect CPZONESUNLOCK:EPERMISIONS If the user has not authorization to the proper partition CPZONESUNLOCK:ENOT_EXISTS If the user with the specified password does not exist CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 115 / 118...
  • Page 116 0) means the zone 1. CPPARTITIONSGETZONES:EPERMISIONS If the specified password is incorrect CPPARTITIONSGETZONES:ENOT_ALLOWED If the command was sent via open SMS CPPARTITIONSGETZONES:EFORMAT If the format of the sent command is incorrect CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 116 / 118...
  • Page 117 0) means the output 1. CPPARTITIONSGETOUTPUTS:EPERMISIONS If the specified password is incorrect CPPARTITIONSGETOUTPUTS:ENOT_ALLOWED If the command was sent via open SMS CPPARTITIONSGETOUTPUTS:EFORMAT If the format of the sent command is incorrect CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 117 / 118...
  • Page 118: Change History

    03.03.2016 / i1.15 / 2.4.7 Added information about new option of “SMS Notifications” 05.04.2016 / i1.16 / 2.4.8 Updated information regarding perimeter zones 24.06.2016 / i1.17 / 2.4.13 Udated information about wireless module antennas. CPX200NWB ALARM CONTROL UNIT – INSTALLER MANUAL 118 / 118...

Table of Contents