IFP-2000 Installation Manual
This product cannot be adjusted or repaired in the field. It must be returned to the factory for
service.
This equipment is not designed for use with party line service. Connection to party line
service is subject to state tariffs. You may contact the state public utility commission, public
service commission or corporation commission for information.
Since the IFP-2000/IFP-2000HV is a commercial fire alarm panel, it must be connected
upstream of all other equipment utilizing the phone lines. If you have questions about the
installation, contact your telephone company or a qualified installer.
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions:
(1) This device may not cause radio interference, and (2) This device must accept any interference received,
including interference that may cause undesired operation.
2.2

Underwriters Laboratories (UL)

2.2.1

Requirements for All Installations

General requirements are described in this section. When installing an individual device, refer
to the specific section of the manual for additional requirements. The following subsections
list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on). See Section 10.7 for
information on releasing operation.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in Section 7.1 (IDP devices) of this manual
and or conventional detectors listed in the compatibility chart
3. Use UL listed notification appliances compatible with the IFP-2000 from those specified
in the Appendix at the back of this manual.
4. A full system checkout must be performed any time the panel is programmed.
2-2
Warning
firealarmresources.com
151430