Miscellaneous Options 2; Strobes Active When Silenced; Auto Display Oldest Event; Ifp-Rpt Repeater Installed - Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual

Analog/addressable fire system
Table of Contents

Advertisement

IFP-2000 Installation Manual
9.6.6

Miscellaneous Options 2

Through this programming option you can turn the strobe synchronization during silence
feature On or Off, and select the control panel to report events by zone or by point.
To edit miscellaneous options 2:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
3. Select
for System Options.
5
4. Select
for Miscellaneous Options 2.
5

9.6.6.1 Strobes Active when Silenced

When "SYNC Strobe:" is Selected as Y (Yes) then strobes will continue to flash when the
system is silenced and will stop flashing when the system is reset.
Note: The "SYNC Strobe:" only functions with outputs that use a synchronized output pattern.
5. Press the
or
6. Press
or

9.6.6.2 Auto Display Oldest Event

When this feature is programmed Y (Yes) then the oldest un-acknowledge event will
automatically display on the control panel and remote annunciators after there has been no
activity on any system touchpad for two minutes.
7. Press the
or
8. Press
or

9.6.6.3 IFP-RPT Repeater Installed

When the "Repeater Installed" option is programmed Y (yes) then panel will supervise the
IFP-RPT Repeater. Set N (no) when an IFP-RPT Repeater is not installed.
9. Press the
or
10. Then press
or
9-32
Initializing
Please wait . . .
arrow to toggle this selection between Y (Yes) or N (No).
to make your selection and move to the next programming option.
arrow to toggle this selection between Y (Yes) or N (No).
to make your selection and move to the next programming option.
arrow to toggle this selection between Y (Yes) or N (No).
.
firealarmresources.com
151430

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silent knight ifp-2000

Table of Contents