9.2.4

View Module List

To view a list of all modules, follow these steps.
You must be in the Main Menu to perform this task. If necessary, enter the Installer Code.
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
3. Press
1
to enter module menu.
4. Press 4 to view list. Use
9.3

Zone

Through the zone option in Panel Programming you can edit, add, delete, and view zone
points. Selections made here affect all detectors and switches in the zone. Up to 999 zones can
be used in each panel.
9.3.1

Edit Zone

Features that can be edited through the edit zone option are, edit zone name, zone properties
(which includes, zone type, and detector sensitivity), and zone accessory options.
To edit a zone, follow these steps:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
3. Press
to enter zone menu.
2
4. Press
to edit a zone.
1
5. Enter the zone number, then press

9.3.1.1 Edit Zone Name

6. Press
to edit the selected zone name.
1
151430
Initializing
Please wait . . .
to scroll though list.
Initializing
Please wait . . .
.
firealarmresources.com
Programming
9-5