4.13.1.2 Class A Notification Wiring

You must use an appliance from the list of compatible appliances in the Appendix at the back
of this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 4-33.
2. Configure the circuit for Class A in programming (see Section 9.5).
Figure 4-33 Class A Notification Appliance Circuit Configuration
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-33 uses both Flexput circuit 1 and 2, so in programming it
would be referred to as point 1.
Maximum voltage drop is 3V per Class A circuit. See Table 4-4
1.0A
1.5A
2.0A
2.5A
3.0A
151430
Supervised
Power Limited
Regulated 24 VDC
3A per Circuit, 9A max Combined
Table 4-4 Maximum Impedance Class A
Current
Maximum Impedance
1.5Ω
1.2Ω
1.0Ω