System Options; Auto Test Time; Phone Lines - Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual

Analog/addressable fire system
Table of Contents

Advertisement

9.6

System Options

This section of the manual explains how to customize software options that affect general
operation of the system. This includes such items as: AC loss hours, system clock options,
holidays schedule, telephone and reporting account options. Refer to each individual
subsection for complete instructions.
9.6.1

Auto Test Time

To access the Auto Test Time screen:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
3. Select
for System Options.
5
4. From the next menu, select
5. Enter the hour you desire the control panel to send an automatic test report (or press the
or
arrow), then press
6. Enter the minutes (or press the
7. Select AM or PM by pressing the
9.6.2

Phone Lines

To access the phone lines screen:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select
for Panel Programming.
7
Display reads:
3. Select
for System Options.
5
4. Select
for the phone lines menu.
1
151430
Initializing
Please wait . . .
for Auto Test Time.
0
.
or
arrow), then press
or
arrow, then press
Initializing
Please wait . . .
firealarmresources.com
Programming
.
.
9-23