City Box Connection Using The 5220 Module - Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual

Analog/addressable fire system
Table of Contents

Advertisement

IFP-2000 Installation Manual

4.15.2 City Box Connection Using the 5220 Module

This section describes how to connect the control panel to a local energy municipal fire alarm
box or "city box" as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire
alarm service. The city (master) box is an enclosure that contains a manually operated
transmitter used to send an alarm to the municipal communication center which houses the
central operating part of the fire alarm system.
City Box Standby Current:
Alarm Current:
The maximum coil and wire resistance (combined) must not exceed 30 ohms.
To install the 5220 for city box connection:
1. Use one of the knockouts on the right side of the control panel to connect the 5220 using a
short piece of conduit (must not exceed 20 feet in length).
2. Wire the 5220 to the control panel as shown in Figure 4-43. This drawing also shows how
to connect the city box coil to terminals 3 and 4 on the 5220. Do not install an EOL resis-
tor in the terminals of the Flexput circuit used for this application.
3. Connect earth ground wire to the 5220 chassis with mounting screw.
4. Program the Flexput circuit as a notification circuit, Refer to Section 9.5.2. Assign this
Flexput to an output group that is mapped to activate with non silenceable constant output
in response to a system general alarm condition.
It is not possible to reset the remote indication until you clear the condition and reset the
control panel.
All circuit off the 5220 are
non- power limited and
all wiring is non-supervised
*The wiring off the main control
is still power limited and supervised
4-44
0 (Notification supervision current
1 Amp for 1 second
27.2 VDC max
Figure 4-43 City Box Connection
firealarmresources.com
accounted for in control panel draw.)
Not suitable for remote
station protected
premise service where
separate transmission
circuits are required for
fire supervisory (if
applicable), and trouble
signals.
Note: Flexput circuit 1
used as an example.
Any flexput circuit
could be used
151430

Advertisement

Table of Contents
loading

This manual is also suitable for:

Silent knight ifp-2000

Table of Contents