order they are listed here.
Important: Connect and address SLC devices before running JumpStart AutoProgramming.
Main Panel Hardware Installation
Mount the control panel cabinet.
Connect AC.
Connect phone lines.
Install 5815XL SLC expander modules (if needed).
Install RA-2000 Remote Fire Alarm Annunciator modules if used.
Install 5865 or LED Annunciator modules if used.
Install 5880 LED I/O module if customized LED annunciation will be used.
Install notification appliances.
Install auxiliary power devices (if used).
If using a printer, install the 5824 Serial/Parallel Printer Interface Module.
Connect batteries (typically last step).
SLC Device Hardware Installation
Perform these steps before running JumpStart AutoProgramming.
Connect device bases to the loop.
Set device addresses.
Physically connect detectors to their bases. Connect relay and contact
monitor modules.
JumpStart AutoProgramming
JumpStart AutoProgramming searches for expanders and SLC devices connected
to the panel but not programmed into the system. JumpStart AutoProgramming
automatically selects some options for SLC devices. See "Input Point
Configuration" section of this chart for other options.
JumpStart AutoProgramming makes selections for the following options. You
can customize options, if necessary.
Device type (detector or switch) configured by JumpStart
AutoProgramming.
Program type of detector (heat, photoelectric, or ionization) selected by
JumpStart AutoProgramming.
System Software Configuration
Select low AC hours report time (3 hours by default).
Enable/disable automatic DST adjustment feature (enabled by default).
Change clock display format (12-hour with AM/PM by default).
Enable/disable day/night sensitivity (disabled by default).
Select holiday schedule (up to 18 days) if installation is using day/night
sensitivity.
Set up reporting accounts.
Select options for phone lines.
Customize banner message (message that displays on LCD in normal
mode) if desired.
Input Point (SLC Device) Configuration
151430
Task
firealarmresources.com
Before You Begin Installing
See Sec.
(for more info.)
4.1
4.2
4.12
4.7
4.5
4.10
4.9
4.13
4.13.5
4.8
4.3
IDP 7.4
IDP 7.5
7.3 & see device
install instructions
8.1 & 9.7
To change, see 9.6
To change, see 9.5
9.6.5.2
9.6.5.3
9.6.5.4
9.6.3
9.6.4
9.6.1
9.6.2
9.6.8