Programming; Ul 864 Programming Requirements - Honeywell SILENT KNIGHT RPS-2000 Installation And Operation Manual

Analog/addressable fire system
Table of Contents

Advertisement

Section 9

Programming

This section of the manual describes how to manually program the control panel from the
built-in annunciator. Each subsection discusses these menu options in detail. All options
described in this section can be performed using the Silent Knight Software Suite (SKSS-2).
Before any customized programming is done, JumpStart AutoProgramming should be
run first. After JumpStart is run, thoroughly test the system. The reason the system
should be tested after JumpStart AutoProgramming is because Jumpstart
AutoProgramming automatically programs the system, searching for and configuring
all SLC and SBUS devices it finds. JumpStart allows you to confirm the integrity of the
installation prior to performing any custom programming. After determining that the
hardware is properly installed, custom programming can be performed. Refer to
Section 8.
9.1

UL 864 Programming Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES: This product incorporates field programmable software. In
order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Programming Option
Misc Options 1
Switch
Phone Line
Misc. Opt 3
151430
Important!
Permitted in
Menu Item
UL 864 (Y/N)
Low AC Report Delay
Water Flow
Enable Gnd Start
Alarm Verification
firealarmresources.com
Possible Settings
Yes
0–30 hours
Yes
latching and non latching
No
Yes & No
Yes
1-250 seconds
Programming
Settings Permitted
in UL 864
1–3
latching
No
60-250 seconds
9-1