11. OPTIONS AND AUXILIARY EQUIPMENT
11.9 No-fuse breakers, fuses, magnetic contactors
Always use one no-fuse breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the no-fuse breaker, use the one having the specifications given in this section.
Servo amplifier
MR-J3-10B (1)
MR-J3-20B
MR-J3-40B 20B1
MR-J3-60B 70B 100B 40B1
MR-J3-200B
www.DataSheet4U.com
MR-J3-350B
MR-J3-500B
MR-J3-700B
Note. This servo amplifier is UL/C-UL-listed when using a Class T fuse. Therefore, when using the servo amplifier as a UL/C-UL
Standard compliant product, be sure to use the Class T fuse.
No-fuse breaker
(Note) Class
30A frame 5A
K5
30A frame 5A
K5
30A frame 10A
K5
30A frame 15A
K5
30A frame 20A
K5
30A frame 30A
K5
50A frame 50A
K5
100A frame 75A
K5
11 - 39
Fuse
Magnetic contactor
Current [A]
Voltage [V]
10
10
15
20
AC250
40
70
125
150
S-N10
S-N18
S-N20
S-N35
S-N50

Advertisement