3. SIGNALS AND WIRING
Device
Speed reached
Limiting torque
www.DataSheet4U.com
Zero speed
Warning
Battery warning
Variable gain
selection
Absolute position
erasing
Connector Pin
Symbol
No.
SA
When using this signal, make it usable by the setting of
parameter No.PD07 to PD09.
When the servo is off, SA will be turned OFF. When servo motor
rotation speed becomes approximately setting speed, SA will be
turned ON. When the preset speed is 20r/min or less, SA always
turns on. This signal cannot be used in position loop mode.
TLC
When using this signal, make it usable by the setting of
parameter No.PD07 to PD09.
When torque is produced level of torque set with controller, TLC
will be turned ON. When the servo is off, TLC will be turned
OFF.
ZSP
When using this signal, make it usable by the setting of
parameter No.PD07 to PD09.
When the servo is off, SA will be turned OFF.
ZSP turns on when the servo motor speed is zero speed
(50r/min) or less. Zero speed can be changed using parameter
No. PC07.
Example
Zero speed is 50r/min
Servo motor
speed
zero speed
(ZSP)
ZPS turns on 1) when the servo motor is decelerated to 50r/min,
and ZPS turns off 2) when the servo motor is accelerated to
70r/min again.
ZPS turns on 3) when the servo motor is decelerated again to -
50r/min, and turns off 4) when the servo motor speed has
reached -70r/min.
The range from the point when the servo motor speed has
reached ON level, and ZPS turns on, to the point when it is
accelerated again and has reached OFF level is called
hysteresis width.
Hysteresis width is 20r/min for the MR-J3-B servo amplifier.
WNG
When using this signal, make it usable by the setting of
parameter No.PD07 to PD09.
When warning has occurred, WNG turns on. When there is no
warning, WNG turns off within about 1.5s after power-on.
BWNG
When using this signal, make it usable by the setting of
parameter No.PD07 to PD09.
BWNG turns on when battery cable breakage warning (92) or
battery warning (9F) has occurred.
When there is no battery warning, BWNG turns off within about
1.5s after power-on.
CDPS
When using this signal, make it usable by the setting of
parameter No.PD07 to PD09.
CDPS is on during variable gain.
ABSV
When using this signal, make it usable by the setting of
parameter No.PD07 to PD09.
ABSV turns on when the absolute position erased.
This signal cannot be used in position loop mode.
Function/Application
OFF level
1)
Forward
70r/min
2)
rotation
ON level
direction
50r/min
0r/min
ON level
Reverse
50r/min
rotation
OFF level
direction
70r/min
ON
OFF
3 - 18
20r/min
(Hysteresis width)
Parameter
No. PC07
Parameter
3)
No. PC07
20r/min
(Hysteresis width)
4)
I/O