Master Programming Level
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following screen:
RANGE 00-23
A flashing cursor will appear in the lower left corner of the display. The factory default setting is
02 hours. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay). When the sec-
ond digit is entered, the display will return to AC Loss Delay Screen #1.

NAC (Notification Appliance Circuit)

The options for the NACs on the control panel main circuit board can be set by pressing 2 while
viewing System Setup Screen #2. The following screens will be displayed:
1=NAC 1
2=NAC 2
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3, or 4 for NAC 4.
Note that 3=NAC 3 and 4=NAC 4 will only be displayed if the NACKEY NAC option card is
installed, in JP8 of the main circuit board, for Class B operation.
AC LOSS DELAY
AC Loss Delay Screen #2
NACS
3=NAC 3
4=NAC 4
NAC Selection Screen
Programming
107