3: Gfann-80 Remote Fire Annunciator; Specifications; Installation; Opening/Closing Annunciator - Honeywell GF505 Manual

Fire alarm control panels
Table of Contents

Advertisement

ANN-BUS Devices
2.8.3 GFANN-80 Remote Fire Annunciator
The GFANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator which mimics the FACP display. It also
provides system status indicators for AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. The GFANN-80 Annunci-
ator provides buttons for remote Reset, Silence, Acknowledge, and Drill of the FACP. Communication between the GFANN-80 and
FACP is accomplished over a two wire serial interface employing the ANN-BUS communication format. The devices are powered, via
two additional wires, from either the host FACP or remote UL-listed, filtered, power supply.

Specifications

Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
 Normal/Standby (no activity): 37.0 mA
 Trouble: 39.0 mA
 Alarm: 40.0 mA
 AC Fail ( not backlit): 15.0 mA
For use indoors in a dry location

Installation

Ensure that all power (AC and DC) has been removed from the FACP before installing the annunciator.

Opening/Closing Annunciator

The following procedure details the steps used to open the annunciator in order to access the terminal block and DIP switches (refer to
figure below):
1.
Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2.
Push in the snap latch located on the right side of the unit while pulling the cover open
3.
To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the cover closed, snapping it shut
4.
Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key

Mounting

The GFANN-80 can be surface or semi-flush mounted to a single, double or 4" square electrical box. Select and remove the appropriate
knockout(s), pull the necessary wires through the knockouts and mount the annunciator in or on the wall depending on the type of instal-
lation desired.
The ANN-SB80KIT(-R/-B/-W) is an available mounting kit for the ANN-80 annunciator. The kit comes with a surface backbox and sur-
face wedge for angled viewing. The two pieces can be used separately or can be stacked together.
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
Annunciator cover
with LCD display
Key switch shown
in ON position
Annunciator backplate
Press in latch
and
Pull annunciator
cover open
Installation
37