Connecting a Releasing Device to the Addressable Control Module

7.5 Connecting a Releasing Device to the Addressable Control Module
The FCM-1-REL module can control 1 A of current. Make sure to keep total system current within the limits of the power supply. Power
for the module must come from the FACP's main power supply or any UL 864-listed 24 VDC regulated, power-limited power supply for
Fire Protective Signaling. For more information, refer to the Device Compatibility Document.
Figure 7.6 shows Class B wiring of the FCM-1-REL.
Figure 7.7 shows Class A wiring of the FCM-1-REL.
Critical Requirements.
When connecting a releasing device to the FCM-1-REL module, note the following:
1.
See "Power Considerations" on page 58 for information on monitoring 24 VDC power.
2.
Do not T-tap or branch a Style Y or Style Z circuit.
3.
Only one (1) 24V solenoid or two (2) 12V solenoids in series can be connected to the FCM-1-REL.
4.
Do not loop wiring under the screw terminals. Break the wire run to provide supervision of connections.
5.
All applications using the FCM-1-REL are power-limited:
• Program the releasing circuit for Type Code REL CKT ULC or RELEASE CKT.
• Circuits are supervised against opens and shorts.
6.
Refer to your FACP's listing documents for instructions on setting the Soak Timer.
(* For legacy panels, refer to FACP programming manual.)
7.
The FCM-1-REL module must be programmed with the correct releasing type code listed in your FACP's listing documents.
(* For legacy panels, refer to FACP programming manual.)
Notifier SLC Wiring Manual — P/N 51253:U5 12/20/2017
Non-resettable 24-VDC power
supply isolated, regulated, power
limited per NFPA 70, listed for fire
protection with battery backup.
Module polarities are shown in alarm
condition. All wiring shown is
supervised and power-limited.
Compatible UL-listed
24 VDC releasing device.
One (1) device maximum.
Non-resettable 24-VDC power
supply isolated, regulated, power
limited per NFPA 70, listed for fire
protection with battery backup.
Module polarities are shown in alarm
condition. All wiring shown is
supervised and power-limited.
Compatible UL-listed
24 VDC releasing device.
One (1) device maximum.
T11
T10
T9
LOOP
Figure 7.6 NFPA Class B Wiring of the FCM-1-REL
Figure 7.7 NFPA Class A Wiring of the FCM-1-REL
FCM-1-REL
T1
ONES
TENS
ADDRESS
FCM-1-REL
T11
T1
T10
T9
ONES
TENS
LOOP
ADDRESS
Control Modules
SLC (-)
SLC (+)
When using the
FCM-1-REL for
Class B
applications,
remove jumper J1.
SLC (-)
SLC (+)
43