7

Maintenance

To maintain the VES-A00-P detector at its peak performance level, the recommended maintenance schedule
shown in Table 7-1 below should be followed.
Table 7-1: Recommended maintenance schedule for the VES-A00-P detector
Maintenance Check
Power Supply and Battery
Check Pipe Network
Pipe Integrity Smoke Test
Check Pipe Flow
Clean Sampling Point
Flush Pipe Network
Replace Filter
Notes:
The above maintenance steps are preventative maintenance.
l
Maintenance can be conducted by the original installer or an authorized distributor or service contractor.
l
The required frequency of maintenance checks may vary depending upon local codes and standards and
l
the environment of the installation.
When smoke testing is done, follow the site procedures for preventing false alarms to monitoring
l
services.
Caution:
While the detector is disabled or put into Standby mode, no fire warnings will be annunciated by
the detector. Prior to any maintenance or testing:
Inform the appropriate supervising authority.
l
Ensure that any ancillary devices dependent on the detector are isolated before work
l
commences.
Attention :
Pendant que le detecteur ou la zone est desactivee, aucun feu d'indication va etre emis par le
detecteur. Avant tout entretien ou tester:
Informer les autorité de supervision appropriée.
l
S'assurer que tout les appareils auxiliaires dépendants sur le détecteur sont isolés avant
l
de commencer aucun travail.
7.1

Standby

When maintenance is performed on the pipe network or sample points it is recommended that you temporarily
set the detector to Standby in order to turn off the aspirator. Setting the VES-A00-P to Standby mode
deactivates the aspirator and stops all detection of alarms (but not detection and signaling of faults). Standby
mode is signaled on relay #1 and relay #3 by default. Other relays may also be configured to signal standby
mode. Refer to sections 4.3.6 and 5.5.12 for further information.
To set the detector to Standby mode using Xtralis VSC, select Go to Standby from the Device menu. The
Disabled LED will blink and the aspirator will turn off. If configured the buzzer will beep once per minute if the
Standby beep checkbox on the Relay configuration screen (section 5.5.12) is ticked.
To re-activate the unit, select End Standby from the Device menu.
www.xtralis.com
Quarterly
Six Monthly
VESDA-E VES-A00-P Product Guide
Annual
Biennial
79