VESDA -E VES-A00-P Product Manual page 78

Table of Contents

Advertisement

VESDA-E VES-A00-P Product Guide
Parameter
Ethernet /WiFi
No timeout
connection idle
timeout (hours)
Smoke Thresholds (See recommendation for lowest Alert in Section 6.)
Alarm Level - Day and
Night - Sector 1 to 4
Alert
0.08 % obs/m
(0.025 % obs/ft)
Action
0.14 % obs/m
(0.044 % obs/ft)
Fire 1
0.20 % obs/m
(0.0063 % obs/ft)
Fire 2
2.0 % obs/m
(0.625 % obs/ft)
Significant Smoke
0.005 % obs/m
(0.0016 % obs/ft)
Change – Logging
Significant Smoke
0.005 % obs/m
(0.0016 % obs/ft)
Change - VESDAnet
Scanning – Sector
8 seconds
Scan Time
Scanning – Scan
3
Delay
Work Days
Monday through
Friday
Day Night Changeover Time
Enabled
Unchecked
l
Day Start
7 AM
l
Night Start
7 PM
l
Holidays
Enabled
Unchecked
l
Start Holiday
Blank
l
Date
End Holiday Date Blank
l
Air Flow
Air flow thresholds
Major High
130%
l
Minor High
120%
l
Minor Low
80%
l
Major Low
70%
l
Delay
30 seconds
Significant Flow
2.0 L/min
Change
72
Table 5-4: Default Settings (continued...)
Default Values
Minimum
15 minutes
0.005 % obs/m
(0.0016 % obs/ft)
0.005 % obs/m
(0.0016 % obs/ft)
0.010 % obs/m
(0.0031 % obs/ft)
0.02 % obs/m
(0.0063 % obs/ft)
0.0001 % obs/m
(0.000031 % obs/ft)
0.0001 % obs/m
(0.000031 % obs/ft)
8 seconds
0
n/a
Unchecked
n/a
n/a
Unchecked
n/a
n/a
105%
105%
25%
25%
15 seconds
0.5 L/min
Range
Maximum
24 hours
2.0 % obs/m
(0.625 % obs/ft)
2.0 % obs/m
(0.625 % obs/ft)
2.0 % obs/m
(0.625 % obs/ft)
20.0 % obs/m
(6.25 % obs/ft)
0.2 % obs/m
(0.0063 % ofs/ft)
0.2 % obs/m
(0.0063 % ofs/ft)
15 seconds
10
n/a
Checked
n/a
n/a
Checked
n/a
n/a
200%
200%
95%
95%
250 seconds
5 L/min
Affected by Return to
Factory Defaults
command
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes