VESDA-E VES-A00-P Product Guide
Command
Start AutoLearn Flow
Cancel AutoLearn Flow
Start AutoLearn Smoke
Cancel AutoLearn
Smoke
54
Table 5-2: Detector Commands (continued...)
Description
Starts the AutoLearn Flow process for the detector.
The detector monitors the environment and
determines appropriate airflow fault thresholds. The
user is prompted to enter the monitoring period.
When the AutoLearn has finished, the flow
thresholds are overwritten.
After AutoLearn is complete, review to confirm that
the thresholds are within ranges allowed by local
codes and standards.
Refer to Chapter 6 on page 75 for more information.
To initiate AutoLearn Smoke and Flow using the
internal AutoConfig button, press and hold the button
until the AutoConfig LED starts flashing
(approximately 15 seconds), then release the button.
Both Autolearn Smoke and Flow will run. The
monitoring period will be 14 days.
Cancels the AutoLearn Flow process.
Flow thresholds will remain at levels set prior to
commencing AutoLearn Flow.
To cancel AutoLearn Smoke and Flow functions
using the internal AutoConfig button, press and hold
the button for 5 seconds. The LED will turn off.
Starts the AutoLearn Smoke process for the
detector. The detector monitors the environment and
determines appropriate smoke thresholds. The user
is prompted to enter the monitoring period.
When the AutoLearn has finished, the smoke
thresholds are overwritten.
After AutoLearn is complete, review to confirm that
the thresholds are within ranges allowed by local
codes and standards.
Refer to Chapter 6 on page 75 for more information.
To initiate AutoLearn Smoke and Flow using the
internal AutoConfig button, press and hold the button
until the AutoConfig LED starts flashing
(approximately 15 seconds), then release the button.
Both Autolearn Smoke and Flow will run. The
monitoring period will be 14 days.
Cancels the AutoLearn Smoke process.
Smoke thresholds will remain at levels set prior to
commencing AutoLearn Smoke.
To cancel AutoLearn Smoke and Flow functions
using the internal AutoConfig button, press and hold
the button for 5 seconds. The LED will turn off.
Execute From
A button
Xtralis VSC
on the
Software
Detector
www.xtralis.com