Maintenance; Replacing The Filter - VESDA VLQ-100 Product Manual

Vlq series
Table of Contents

Advertisement

VESDA by Xtralis
8

Maintenance

To maintain the VESDA VLQ detector at its peak performance level, the recommended maintenance
schedule shown in Table 8-1 below should be followed.
Table 8-1: Recommended maintenance schedule for the VESDA VLQ detector
Maintenance Check
Power Supply and Battery
Check Pipes
Pipe Integrity Smoke Test
Check Pipe Flow
Clean Sampling Points
Flush Pipe Network
Replace Filter
8.1

Replacing the Filter

The detector reports a fault condition on the front panel and in the event log to indicate that the filter requires
replacement after the recommended period of time has elapsed, or filter use percentage limit reached,
whichever occurs first.
After removing the old filter and prior to inserting the new one, it is necessary to reset the filter used
percentage value. This can be done using the detector controls or from within Xtralis QSC.
Requirements
Philips head screwdriver
Filter Removal Procedure
1. Rotate cover 45° counter-clockwise and remove by lifting outwards (Figure 8-1).
2. Release the filter:
Where the filter is secured with a retaining bracket: Remove screws (C) with a Philips head
l
screwdriver and lift out the filter retaining bracket (D) (Figure 8-2).
www.xtralis.com
Quarterly
A
Figure 8-1: Remove the Detector Cover
VESDA VLQ Product Guide
Six-monthly
Annual
Biennial
B
37