VESDA-E VES-A00-P Product Guide
5.5.11 General Purpose Inputs Options
The General Purpose Inputs options page provides the ability to control the behavior of the Unmonitored and
Monitored General Purpose Inputs (GPIs).
The GPIs can be configured to initiate a number of different actions.
The configuration options are as follows:
GPI function (Unmonitored) and GPI function (Monitored): Refer to Table 5-3 below for a description
l
of the individual selections.
Button Lockout: If the checkbox is ticked the Reset, Disable and Acknowledge functions can't be
l
executed using the front panel button.
Function
External Reset
Unmonitored GPI
The detector resets on a 0 VDC to 5 VDC
rising edge.
Monitored GPI
The detector resets on a contact closure.
66
Figure 5-22: General Purpose Input Options
Table 5-3: GPI Operation
State Change
5V
0V
Reset
Closed
Open
Reset
www.xtralis.com