Commissioning checklist for the Remote Display/Relay – If used.
Commissioning Checks
Zone number configured.
Have checked that no faults are reported.
The alarm and fault relay outputs are wired to the fire
panel.
Test the Remote Display/Relay's Relay output
connections to the fire panel using the Xtralis VSC Relay
Test command. (Turn each relay on/off individually.) See
below.
Relay 1 Tested (Default assignment = Disable)
Relay 2 Tested (Default assignment = Minor Fault)
Relay 3 Tested (Default assignment = Urgent Fault)
Relay 4 Tested (Default assignment = Alert)
Relay 5 Tested (Default assignment = Action)
Relay 6 Tested (Default assignment = Fire 1)
Relay 7 Tested (Default assignment = Fire 2)
Relay 8 Tested (Default assignment = Sector 1)
Relay 9 Tested (Default assignment = Sector 2)
Relay 10 Tested (Default assignment = Sector 3)
Relay 11 Tested (Default assignment = Sector 4)
Relay 12 Tested (Default assignment = Scanning)
Alert, Action, Fire 1, Fire 2 Alarm and First alarm sector
connection to Fire Panel for each sector tested using the
Xtralis VSC Alarm Test Command
Sector 1:
Fire 2
Fire 1
Action
Alert
First Alarm
Sector 2:
Fire 2
Fire 1
Action
Alert
First Alarm
Sector 3:
Fire 2
Fire 1
Action
Alert
First Alarm
www.xtralis.com
VESDA-E VES-A00-P Product Guide
Done (Y/N)
Notes