INSTALLATION MANUAL
VLP Models
VLP-000
VLP-002
VLP-012
VLP-400
October 2005
Version 1.5
A LaserPLUS
A

Advertisement

Table of Contents
loading

Summary of Contents for VESDA LaserPLUS VLP-000

  • Page 1 A LaserPLUS ™ INSTALLATION MANUAL VLP Models VLP-000 VLP-002 VLP-012 VLP-400 October 2005 Version 1.5...
  • Page 2 Disclaimer The manufacturer reserves the right to change designs or specifications without obligation and without further notice. VESDA, LaserTEKNIC, LaserPLUS, LaserSCANNER, LaserCOMPACT, LaserFOCUS, VESDAnet, VESDAlink, ASPIRE, AutoLearn, VSM, VConfig, InfoWORKS, PROACTIV, PRECISION and VSC are trademarks used under licence by the distributor.
  • Page 3 VESDA ® LaserPLUS Installation Manual Figure 1 The Laser Warning Label Version 1.5...
  • Page 5: Table Of Contents

    Power Up ........................18 Power Up the System ....................18 Preliminary System Checks ..................19 Logging On to the System....................19 VESDAnet Communication Check ................19 Normalise the Air Flow and Clearing Air Flow Faults............20 Basic Pass/Fail Smoke Test..................21 Installation Checklist ....................22 VESDA Product Warranty Conditions ..............23...
  • Page 6: Introduction

    This manual is intended for installation technicians to be able to install, perform basic power and preliminary device checks for the LaserPLUS detector. It does not cover information for commissioning. All VESDA equipment is to be commissioned by personnel who have attended a VESDA accreditation course.
  • Page 7: Cabling Requirements

    VESDA ® LaserPLUS Installation Manual 2. Cabling Requirements The terminals on the termination card in the LaserPLUS will accept wire sizes up to 2.5sq mm (12 AWG). 2.1 Power Cables Use the power ratings for the detector and the modules to determine the required wire sizes.
  • Page 8: Laserplus Specifications

    VESDA ® LaserPLUS Installation Manual 3. LaserPLUS Specifications Supply Voltage 18 to 30VDC Power Consumption See table 1, page 3 Dimensions (WHD) 350mm x 225mm x 125mm (13.8in x 8.9in x 4.9in) Weight 4.0kg (9lbs) including Display and Programmer module Operating Temperature Tested to: -10°C to 55°C (14°F to 131°F)
  • Page 9: Laserplus Dimensions

    VESDA ® LaserPLUS Installation Manual 4. LaserPLUS Dimensions 350 (13.8) 51.0 35.0 (1.37) (2.0) 21.0 (0.83) Bridge and Lance (7.87) (8.9) 77.5 (3.05) 28.5 (1.12) 209 (8.24) (12.56) 207 (8.15) Mounting Bracket 12.0 (0.47) CE = Cable Entry Ports (25.4mm, 1.0in ∅)
  • Page 10 VESDA ® LaserPLUS Installation Manual 350(13.8) 34.0 45.0 (1.37) (1.33) (1.33) (1.33) (1.33) (1.77) 26.0(1.02) 26.0 (1.02) Inlet Air Ports TOP VIEW 26.0 125 (4.9) (1.02) (8.9) 28.5 (1.12) RIGHT HAND LEFT HAND FRONT VIEW SIDE VIEW SIDE VIEW BOTTOM VIEW 26.0...
  • Page 11: Battery Backup Calculations

    5. Battery Backup Calculations The nominal supply voltage is 24 VDC. Use Table 2 to calculate and to determine the battery backup requirements for your VESDA system. Refer to Table 1, page 3 for power consumption details. NORMAL LOAD @ 24 V DC...
  • Page 12: Installation

    VESDA ® LaserPLUS Installation Manual 6. Installation 6.1 Check Procedure Before Installation (a) Do not install your LaserPLUS if there are any signs of shipping damage. Inform your distributor if there is any damage. (b) Check the model of the LaserPLUS is correct as per the design specifications for the site.
  • Page 13: Removal Of

    VESDA ® LaserPLUS Installation Manual Note: For LaserPLUS detectors mounted in the Inverted Orientation position, the display and/or programmer modules have to be rotated 180°. Refer to Section 6.4 for procedure to rotate the modules. The position of the Programmer and Display modules can be interchanged.
  • Page 14: Component Location Inside Detector Enclosure

    VESDA ® LaserPLUS Installation Manual 6.3 Component Location inside Detector Enclosure CPU Card Wire Terminal Strips (Under Backing Sheet) Termination Card (7 Relays) VESDAnet socket Aspirator FOK LED Connector VESDAnet Laser Detector Air Filter Cartridge Number Chamber Figure 5 Components inside Detector Enclosure 6.4 Display and Programmer Module Orientation...
  • Page 15: Removal Of Metal Knockout Holes For Cable Entry

    VESDA ® LaserPLUS Installation Manual 6.5 Removal of Metal Knockout Holes for Cable Entry (a) Determine the cable entry holes to be used. Refer to Figure 7. (b) Using the ball end of a small hammer, gently tap onto the required knockout holes to break away the metal pieces.
  • Page 16: Securing The Mounting Bracket

    VESDA ® LaserPLUS Installation Manual 6.7 Securing the Mounting Bracket Warning: Make sure that there are no electrical wires or plumbing behind the mounting position before drilling. Ensure the mounting position is flat. a) Remove the drilling template from the centre page of this manual.
  • Page 17: Connecting The Air Sampling Pipe

    VESDA ® LaserPLUS Installation Manual 6.9 Connecting the Air Sampling Pipe The air inlet ports are designed to fit a standard pipe of 25mm (1in) OD. A tapering of the air inlet ports prevent the pipes from being inserted beyond 15mm (5/8in).
  • Page 18: Termination Card Details

    VESDA ® LaserPLUS Installation Manual 6.11 Termination Card Details Terminal A Terminal B Terminal C Pin 1 Pin 1 Pin 1 Terminal A Terminal B Terminal C 1 VESDAnet A+ 1 Isolate (NO) 1 Fire 2 (NC) 2 VESDAnet A-...
  • Page 19: Terminating The Power Wires To The Termination Card

    VESDA ® LaserPLUS Installation Manual 6.13 Terminating the Power Wires to the Termination Card a) Refer to Figure 9 for the location of the power terminals on the termination card. b) Connect the power wires to the Power terminals as shown in Figure 10.
  • Page 20: Terminating The Relay Wires To The Termination Card

    VESDA ® LaserPLUS Installation Manual Detector 1 Detector 2 Detector 3 ½ Terminal A ½ Terminal A ½ Terminal A Shield Shield Shield Shield Shield Shield Shield Shield Shield Shield Detector 5 Detector 4 ½ Terminal A ½ Terminal A Figure 11 Wire Connection Details for VESDAnet (Closed Loop) ½...
  • Page 21: Closing Up The Laserplus

    VESDA ® LaserPLUS Installation Manual Terminal B Terminal C Fire 2 Isolate (Relay 7) (Relay 1) Minor Fault Fire 1 (Relay 2) (Relay 6) Urgent Fault Action (Relay 3) (Relay 5) GPI- Alert GPI+ (Relay 4) Terminal Pins location for 7 Relays (Default Relay Assignments) Figure 13 Wire Termination Details for 7 Relays 6.16 Closing Up the LaserPLUS...
  • Page 22: Power Up

    The aspirator starts up and air is felt flowing out of the exhaust port. If a Programmer module is fitted, the VESDA name will appear on the LCD screen. If a Display module is fitted, the following indicators are lit:- •...
  • Page 23: Preliminary System Checks

    VESDA ® LaserPLUS Installation Manual 8. Preliminary System Checks Perform the following preliminary system Setup and checks before commissioning. (a) Logging onto the system with a PC or a LCD Programmer. See Section 8.1. (b) VESDAnet communication checks. See section 8.2 (c) Normalise the airflow.
  • Page 24: Normalise The Air Flow And Clearing Air Flow Faults

    VESDA ® LaserPLUS Installation Manual Procedure LCD Programmer PC Programmer • Select Show Wiring Order ↵. • Select the Device Tree command Display the VESDAnet numbers. from the View menu. • Read the displayed devices • From the Device Tree window, and VESDAnet numbers.
  • Page 25: Basic Pass/Fail Smoke Test

    VESDA ® LaserPLUS Installation Manual 8.4 Basic Pass/Fail Smoke Test Note: This test verifies the detector will sense smoke. It does not replace any appropriate commissioning test. Use the table below to perform this test by using one of the following devices.
  • Page 26: Installation Checklist

    VESDA ® LaserPLUS Installation Manual 9. Installation Checklist Site Name: ……………………………………………………………………… Zone: …………………………………………………………………………….. Detector Serial Number/s: …………………………………………………… Perform the following checks listed below to ensure that all the necessary items are completed before handing over to a commissioning engineer. INSTALLATION CHECKS 1.
  • Page 27: Vesda Product Warranty Conditions

    LaserPLUS Installation Manual 10. VESDA Product Warranty Conditions 1. Vision Systems warrants that new VESDA products (excluding consumable items) will conform to its published specifications and remain in good working order during the warranty period of 24 (twenty four) months from date of shipment from Vision Systems.
  • Page 29 Australia and Asia The Americas Europe and the Middle East Vision Fire & Security Vision Fire & Security Vision Fire & Security Private Bag 215 700 Longwater Drive Vision House, Focus 31 Mark Road 495 Blackburn Road Norwell, MA 02061, USA...