VESDA-E VES-A00-P Product Guide
Table 2-2: VES-A00-P Detector Specifications (continued...)
Specification
Sensitivity Range
Threshold Setting Range
Referencing
Event Log
AutoLearn
Referencing
Four Alarm Levels
Two Fault Warning Levels
Maintenance Aids
VESDA-E VES-A00-P Detector
Exhaust Adaptor US
Note:
Refer to Table 7-2 for the spare parts list.
10
Value
0.005 to 20% obs/m (0.0016 to 6.25% obs/ft.)
Alert: 0.005%–2.0% obs/m
l
(0.0016% - 0.625% obs/ft)
Action: 0.005%–2.0% obs/m
l
(0.0016% - 0.625% obs/ft)
Fire1: 0.010 %–2.0% obs/m
l
(0.0031% - 0.625% obs/ft)
Fire2: 0.020 %–20.0% obs/m
l
(0.0063% - 6.25% obs/ft)
Notes:
UL and ULC: For open area, open area high velocity and
l
duct protection the fire alarm threshold (setting) that
initiates an evacuation signal must be set such that the
sensitivity of each sampling hole is more sensitive than
10%/m (3.2%/ft) as determined by the ASPIRE software.
Refer to Section 5.6 on page 71 for the default settings.
l
Reference smoke level source.
Table 2-3: Key Software Features
Up to 20,000 events stored on FIFO basis
Minimum 15 minutes
l
Maximum 15 days, 23 hrs, 59 minutes
l
Recommended 14 days
l
Thresholds are automatically changed from the previously set
values to the updated values after the AutoLearn process has
completed.
Adjustment for external ambient conditions
Alert, Action, Fire1 and Fire2
Maintenance and Major Fault
Filter and flow monitoring
l
Event reporting via VESDAnet and event log
l
Table 2-4: Ordering Information
VES-A00-P
VSP-961
www.xtralis.com