Installation; Prepare The Detector - VESDA -E VES-A00-P Product Manual

Table of Contents

Advertisement

4

Installation

The VES-A00-P detector is shipped with the following components:
1 VESDA-E VES-A00-P detector
l
Installation Sheet
l
Mounting bracket
l
Mounting template for directly mounting the detector to the mounting surface
l
Exhaust Adaptor (US only)
l
1 End of Line resistor for the monitored GPI
l
Check all components for damage and refer any concerns to your authorized representative.
Depending on the nature of the installation, it may be necessary to procure the following items:
The latest revision of this full product guide can be downloaded from the partner extranet at
l
www.xtralis.com.
A 24 VDC Power Supply and backup battery, compliant with local fire protection codes and standards
l
Screws and inserts for the mounting bracket that are appropriate for the installation location.
l
Type A to Type B USB Interface Lead, required for initial configuration of the detector (Figure 4-1).
l
Wrist strap for ESD prevention.
l
4.1

Prepare the Detector

Remove tape from the exhaust port.
l
Invert the fascia if required. Refer to Section 4.2.1 for further information.
l
Remove cable and pipe inlet plugs as required. Place a large screwdriver in the large slot and twist (A), or
l
use a small screwdriver in the side slots (B) to lever the plug out (Figure 4-2). Use the edge of the
detector (C) for a lever point to avoid marking the case.
www.xtralis.com
Figure 4-1: Type A to Type B USB Interface Lead
A
Figure 4-2: Remove Cable and Pipe Inlet Plugs
VESDA-E VES-A00-P Product Guide
B
C
17