3.4 Installing Optional EIB (Controller Extended Interface Board)

An EIB (Controller Extended Interface Board) can be installed inside the distribution cabinet. This option is factory installed if ordered
with the system. Refer to the following procedure to field install this option.
Procedure
1.
Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these
alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system
while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to
inadvertently contact or have any tool inadvertently contact any energized electrical termination.
2.
Open the distribution cabinet's front door.
WARNING! Damage to the circuit card may result if the next step is not followed.
3.
Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
4.
Set the switch on the EIB board as outlined in "Switch Settings on Optional EIB (Controller Extended Interface Board)" on
page 13.
5.
Refer to Figure 3.3 and install the EIB board inside the distribution cabinet.
6.
Locate the I2C connector bundled at the bottom of the distribution cabinet. Route this cable to the newly installed EIB board.
Cut cable ties as required. Plug this connector into the mating I2C connector located on the EIB board. Refer to Figure 3.3.
Dress and secure the cable as required.
7.
Make external connections to the EIB board as required. See "Optional EIB (Controller Extended Interface Board)
Connections (if required)" on page 26.
8.
Remove the grounding wrist strap.
9.
Reboot the Controller
Local Menu Navigation: At the Main Screen, press ENT and ESC at the same time to reset the NCU Controller.
Web Menu Navigation: Go to Advance Settings Menu / SW Maintenance Tab / Reboot Controller button.
10.
Close the distribution cabinet's front door.
11.
Enable the external alarms or notify appropriate personnel that this procedure is finished.
12.
Ensure that there are no local or remote alarms active on the system.