Making Electrical Connections; Important Safety Instructions; Wiring Considerations - Vertiv NetSure 7100 Installation Manual

-48 vdc power system
Hide thumbs Also See for NetSure 7100:
Table of Contents

Advertisement

Vertiv™ NetSure™ 7100 -48 VDC Power System Installation Manual

5 Making Electrical Connections

5.1 Important Safety Instructions

DANGER! Adhere to the "Important Safety Instructions" starting on page v.

5.2 Wiring Considerations

All wiring and branch circuit protection should follow the current edition of the American National Standards Institute (ANSI)
approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), and applicable local codes. For operation in
countries where the NEC is not recognized, follow applicable codes.
For wire size, branch circuit protection, crimp lug, and general wiring recommendations; refer to System Application Guide
SAG582127000.
Lugs should be crimped per lug manufacturer's specifications.
Refer to Table 5.1 for supplemental lug crimping information when using the special application crimp lug / strap combination.
Table 5.1: Supplemental Lug Crimping Information when using the Special Application Crimp Lug / Strap Combination
Crimp Lug Part No.
245393500
245393600
245393700
245393800
514872
514873
1
The lugs should be crimped to the specifications given in the manufacturer's instructions furnished with the crimp tool or lug.
14
T&B Model TBM12 or TBM15 Hydraulic Heads
Color Key
Burndy:
Pink
YA25L-4TCG1
Burndy:
Black
YA26L-4TCG1
Burndy:
Orange
YA27L-4TCG1
Burndy:
Purple
YA28L-4TCG1
T & B:
256-30695-1879
Yellow
Burndy:
YA29L-4TCG1
T & B:
256-30695-1880
Red
Burndy:
YA31L-4TCG1
Crimp Tool Required
1
,
Die Index/
Die Cat.
Code No.
Number
42H
15508
45
15526
50
15530
54H
15511
62
15510
71
15514