Vertiv™ NetSure™ 7100 -48 VDC Power System Installation Manual

6 Installing Rectifier Modules

Rectifiers can be inserted or removed with power applied (hot swappable).
NOTE!
Each rectifier locks into the module mounting assembly by means of a latch located on the bottom of the rectifier.
The latch and rectifier handle are interactive. Pushing the handle up into the rectifier's front panel causes the latch to extend
to the locking position; pulling the handle down out from the rectifier's front panel causes the latch to retract. See Figure 6.1.
WARNING! To prevent damage to the latching mechanism, ensure the handle is in the open position when installing or
removing a rectifier. NEVER hold the handle in the closed position when installing a rectifier into a shelf.
Procedure
1.
Unpack the rectifiers.
2.
If present, remove blank cover panels from the module mounting positions into which rectifiers are to be installed.
3.
Place the rectifier into an unoccupied mounting position without sliding it in completely.
4.
Loosen the captive screw on the rectifier's handle. Pull the handle down out from the rectifier's front panel (this will also
retract the latch mechanism). See Figure 6.1.
5.
Push the rectifier completely into the shelf.
6.
Push the handle up into the rectifier's front panel. This will lock the rectifier securely to the shelf. Tighten the captive screw
on the handle.
7.
Repeat the above steps for each rectifier being installed in the system.
8.
After the rectifiers are physically installed in the mounting assembly(s), they are ready for operation immediately after power
is supplied to them.
Figure 6.1: Installing Rectifiers
36
Latch
Screw
Handle
Open the handle