3.3 Installing Optional Lug Adapter Busbar Kits

These kits provide lug adapter busbars plus hardware for use with 2-pole and 3-pole circuit breakers. A right-angle kit is also
available for 1-pole devices.
Procedure
1.
Refer to Figure 3.2 to install the lug adapter busbars kits.
Figure 3.2: Installing Optional Lug Adapter Busbar Kits
559803
559804
Busbar Adapter
Kit P/N 559805
Load Return
Connections
-48 VDC Load
Connections
-48 VDC Load
Connections
4
Apply anti-oxidizing compound to busbar mating surfaces
before assembling. Recommended torque is 75 in-lbs
using the supplied 1/4" bolts and hardware. Recommended
559805
torque is 300 in-lbs using the supplied 3/8" bolts and hardware.
Busbar Adapter
Kit P/N 559804
Circuit breaker locations for reference only.
Busbar Adapter
Kit P/N 559803