To set the Transmitter URV with reference pressure:
Set the transmitter applied pressure as for Upper Range value (100%). Navigate the Digital LCD Integral
Display menu, select
Device Config
Select
OK
to start the autoadjust.
Digital LCD Integral Display Keys sequence to set the URV wih pressure: 2 – 1 – 1 – 2 – OK

Set the URV by CoMeter

URV configuration by CoMeter is available with the 695 Field Indicator. Please refer to the device manual for
the appropriate operations.

Set the URV by HHT

URV configuration by Hand Held Terminal is available. Please refer to the device manual for the appropriate
operations.

Set the URV by PC

URV configuration by PC is available using dedicated Software. ABB can provide the references and the
Software. Please refer to the Software instructions for the appropriated operations.

Set the Totalizer

When a Totalizer setting different from the selected is needed it is possible to change it following one of the
methods described in the next paragraphs.
In case the Totalizer is used in Bidirectional Flow the Totalizer LRV (0%) and the Totalizer URV (100%) have
to be equal in absolute value.

Set the Totalizer by Digital LCD Integral Display

To set the Totalizer LRV (0%):
Navigate the Digital LCD Integral Display menu, select
and the value will be available. To modify select
color with the up and down keys and confirm with
confirm with
OK.
Note: the minimum and the maximum values to introduce is indicated on the display.
Digital LCD Integral Display Keys sequence to set the Totalizer LRV : 4 – 3 – 1 – Edit
To set the Totalizer URV (100%):
Navigate the Digital LCD Integral Display menu, select
and the value will be available. To modify select
color with the up and down keys and confirm with
confirm with
OK.
Note: the minimum and the maximum values to introduce are indicated on the display.
Digital LCD Integral Display Keys sequence to set the Totalizer URV : 4 – 3 – 2 – Edit
To set the Input Totalizer Engineering Units:
Navigate the Digital LCD Integral Display menu, select
the used Totalizer Engineering Units will be available. To modify select
the following table) with the up and down keys and confirm with OK.
Digital LCD Integral Display Keys sequence to set the Totalizer Input Engineering Units : 4 – 3 – 3 – Edit
>
Rerange
>
Rerange with pressure
Totalizer
Edit
then scroll the desired value for the digit in reverse
Next.
Repeat the operation for the seven digits and
Totalizer
Edit
then scroll the desired value for the digit in reverse
Next.
Repeat the operation for the seven digits and
Totalizer
>
Set URV
(100%).
>
Totalizer setting
>
Totalizer LRV
>
Totalizer setting
>
Totalizer URV
>
Totalizer setting
>
Input Eng.
Edit
then scroll the desired unit (see
29
(0%),
(100%),
Units, and
Configuration