Software Settings; Write Protect Mode; Change The Failsafe Direction; Set The Current Output Limits - ABB 2600T Pressure Transmitter Series User Manual

Table of Contents

Advertisement

364xS User's Manual
Check the Software failsafe direction is set to Hardware before the
operation. Position the left dip switch in L for fail low (i.e. output
current: 3.7 mA)
Check the Software failsafe direction is set to Hardware before the
operation. Position the left dip switch in H for fail high (i.e. output
current: 22 mA)

Software settings

Write protect mode

Changes can be prevented to the transmitter configuration data with the write protection electronics dip
switch 1. If the transmitter write protection is activated the transmitter will not accept any writes to its
memory. Configuration changes, such as trim and reranging cannot take place. In case the Digital LCD
Integral Display is installed the Write protect mode can also be set by HART command using the HHT and
the PC. Please refer to the device manual and Software instruction for the right operation.

Change the failsafe direction

The transmitter alarm direction is set selecting the Failure Mode in the transmitter software. The output value
is in accordance with NE43 NAMUR recommendations.
Navigate the Digital LCD Integral Display menu, select
the Failure Mode in use will be visible. To modify select
following table) with the up and down keys and confirm with OK.
As per Dip-Switch
Fail High
Fail Low
Digital LCD Integral Display Keys sequence to change the failsafe direction: 2 – 4 – 1 - Edit

Set the Current Output limits

When the Current Output limits on alarm and saturation different from the selected is needed it is possible to
change it following one of the methods described in the next paragraphs.

Set the Current Output limits on the Digital LCD Integral Display

To set High Saturation current
Navigate the Digital LCD Integral Display menu, select
High Saturation
> Edit, and the value change will be possible. Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the High saturation current: 2 – 4 – 2 – 1 – Edit
To set Low Saturation current
Navigate the Digital LCD Integral Display menu, select
Low
Saturation> Edit, and the value change will be possible. Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the Low saturation current: 2 – 4 – 2 – 2 – Edit
To set Fail High current
Navigate the Digital LCD Integral Display menu, select
Fail
High> Edit, and the value change will be possible. Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the Fail High current: 2 – 4 – 2 – 3 - Edit
Device config
Edit
then scroll the desired Failure Mode (see the
to give the Failure Mode control at the Hardware setting
to set the Failure Mode in high current condition (the value can be set
by the user following the appropriate procedure of this manual)
to set the Failure Mode in low current condition (the value can be set
by the user following the appropriate procedure of this manual)
Device config
Device config
Device config
L
H
L
H
>
Output on alarm
>
Failure Mode
>
Output on alarm
>
Set Fail Current
>
Output on alarm
>
Set Fail Current
>
Output on alarm
>
Set Fail Current
38