ABB 2600T Pressure Transmitter Series User Manual page 67

Table of Contents

Advertisement

364xS User's Manual
According to CSA International Standards which can assure compliance with Essential Safety Requirements
C22.2
0-M1991 :
General Requirements – Canadian Electrical Code Part II.
0.4-M1982 :
Bounding and Grounding of Electrical Equipment (Protective Grounding)
0.5-M1982 :
Threaded Conduit Entries
25-M1966 :
Enclosures for use in Class II Groups E, F and G Hazardous Locations.
30-M1986 :
Explosion-proof Enclosures for use in Class I Hazardous Locations.
94-M1991 :
Special Purpose Enclosures.
213-M1987 :
Non-Incendive Electrical Equipment for use in Class I Division 2 Hazardous Locations.
157-M1992 :
Intrinsically Safe and Non-Incendive Equipment for use in Hazardous Locations.
CAN/CSA C22.2 No.1010.1-92
Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1 : General
Requirements (includes Amendment 1)
CAN/CSA C22.2 No.1010.1B-97
Amendment 2 to CAN/CSA C22.2 No 1010.1-92
CAN/CSA E60079-0-00
Electrical apparatus for explosive gas atmosphere. Part 0 : General Requirements.
CAN/CSA E60079-1-01
Electrical apparatus for explosive gas atmosphere. Part 1 : Construction and verification test of flameproof enclosure of
electrical apparatus.
CAN/CSA E60079-11-02
Electrical apparatus for explosive gas atmosphere. Part 11 : Intrinsic Safety "i"
The 2600T Series pressure transmitters have been certified by CSA International for the following Class, Divisions and
Gas groups, hazardous classified locations, temperature class and types of protection.
Explosionproof for Class I, Division 1 and 2, Groups A, B, C and D; Class II Groups E, F and G; Class
III; Enclosure Type 4X Ex d IIC.
Non incendive for Class I, Division 2, Groups A, B, C and D; Class II Groups E, F and G; Class III;
Enclosure Type 4X Ex nL IIC.
Intrinsically Safe for Class I, Division 1 and 2, Groups A, B, C and D; Class II Groups E, F and G;
Class III; Enclosure Type 4X Ex ia IIC.
Temperature class T4 to T6 (dependent on the maximum input current and the maximum ambient
temperature).
Ambient Temperature range -50°C to +85°C (dependent on the maximum input current and the
maximum temperature
class).
Electrical Supply range Minimum 10.5 Volts, Maximum 42 Volts (dependent on the type of protection,
maximum ambient temperature, maximum temperature class and communication protocol).
Type 4X applications Indoors & Outdoors.
Pollution Degree I
Installation Category II
Altitude 2000 m
Humidity 0 to 80%
For a correct installation in field of the 364 pressure transmitter models please see the related control
drawing.
Note that the associated apparatus must be CSA approved.
67
Additional Safety

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

364ds364ps

Table of Contents