Configuration; Default Configuration; Easy Setup - ABB 2600T Pressure Transmitter Series User Manual

Table of Contents

Advertisement

364xS User's Manual

Configuration

Default configuration

The data default configuration at the product delivery is the following:
Pressure Polarity:
Damping:
Units:
LRV:
URV:
Totalizer:
Transfer function:
Hardware setting:
Low saturation current:
High saturation current: 20.5 mA
Low fail current:
High fail current:

Easy Setup

To facilitate commissioning the 364 Display has the capability to run a sequence of predefined setup steps
with the main configuration settings.
When you start the Easy Setup you must continue up to the end to exit.
To start the Easy Setup:
Navigate the Digital LCD Integral Display menu, select
Digital LCD Integral Display Keys sequence to start the Easy Setup: 1
Define the language
If the desired language is different from the indicated language select
(see the following table) with the up and down keys and confirm with OK. Select
English
German
Define the Pressure Polarity
If the desired High Pressure side is different from the indicated select
Pressure side (see the following table) with the up and down keys and confirm with OK. Select
continue.
P2 = High pressure
P1 = High pressure
Define the Engineering Unit
If the desired Engineering Unit is different from the indicated, select
following table) with the up and down keys and confirm with OK. Select
mbar
millibar
2
g/cm
grams per square centimeter
2
Kg/cm
kilo grams per square centimeter
Pa
pascal
kPa
kilopascal
torr
torr
atm
atmosphere
MPa
Megapascal
inH2O°C
inches of water at 4 degrees Celsius
P2 High pressure
1 second
kPa
0 kPa
equal to URL
OFF
linear
Write protect mode in OFF, Failsafe direction High
3.8 mA
3.7 mA
22 mA
Spanish
French
the high pressure side is the pressure chamber indicated as P2 on
the transmitter body. The output pressure will be P2 – P1
the high pressure side is the pressure chamber indicated as P1 on
the transmitter body. The output pressure will be P1 – P2
mmH2O°C
inH2O°F
inHg°C
ftH2O°F
mmH2O°F
mmHg°C
psi
bar
Easy
Setup.
Edit
then scroll the desired language
Italian
Edit
then scroll the desired High
Edit
then scroll the desired unit (see the
Next
to continue.
millimeter of water at 4 degrees Celsius
inches of water at 68 degrees Fahrenheit (20°C)
inches of mercury at 0 degrees Celsius
feet of water at 68 degrees Fahrenheit (20°C)
millimeter of water at 68 degrees Fahrenheit (20°C)
millimeter of mercury at 0 degrees Celsius
pounds per square inch
bars
22
Next
to continue.
Next
Configuration
to

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

364ds364ps

Table of Contents